CT definition
There are 2 CT as standard accessories of
ESS-MET.
1P2W system: Only one CT need to be installed.
1P3W system: Two CTs need to be installed.
The CT must be installed at the point of common coupling(PCC).
According to the system connection(1P2W / 1P3W), please refer the figure below to install the
CTs and wiring cables.
1P2W system
1. Wiring AC input cables to the terminals, Line, Neutral, Ground.
2. Placing the CT at the point of common coupling of hot wire(Line) so that the CT is able to
measure the current which includes
ESS-INV
and load.
3. The direction of CT is from grid to load.