2-5. AC Input/Output Installation
Note:
Please install an AC breaker between the inverter and
utility grid before wiring to utility grid.
Step 1:
Confirm whether the utility grid voltage and frequency are within the inverter specifications.
Step 2:
Before installing the AC input/output of the inverter, please confirm whether the circuit breaker
connected to the utility grid is open. The utility grid circuit breaker can only be closed when the
electrical installation of the photovoltaic inverter is completed.
Step 3:
Remove the AC output cover.
Step 4:
Wire the AC output according to the recommended wire diameter and the steps shown in the
figure below.
Recommended AC output wiring wire diameter
Model
Diameter Φ(mm) Area (mm
2
)
AWG no.