48 Error resolution and maintenance
Taking the Wallbox eM4 Single out of operation
In case of severe malfunctions or damage to the device, you must take the Wallbox eM4 Single out of operation.
To do so, proceed as follows:
1
Unlock the wallbox’s side RCCB flap using the key supplied
and flip it up.
2
Flip the toggle switch of the RCCB to the
0
position.
1
+
0
1
0
3
Close the RCCB flap and lock it with the key.
4
Open your domestic power distribution box, disconnect the
wallbox’s power supply cable from the electricity grid via the
MCB, secure the MCB against being switched on again and
close the distribution box.
1
0
The Wallbox eM4 Single is no longer connected to the electricity grid and can be removed by a qualified specialist electrical contractor
if required.
DANGER
Dangerous electrical currents
Note that the Wallbox eM4 Single is only powered off when the upstream MCB in the domestic power distribution is switched off
(position
0
). The wallbox’s internal RCCB only disconnects the power module from the mains, but the internal electronic compo-
nents remain connected to the mains.
DANGER
Dangerous electrical currents
Always make sure the supply cable is voltage-free before you start dismantling the wallbox.