5 Troubleshooting
XSeriesG4 Remote Controller User's
manual
2103334 Rev. AB
| 93
COLD start procedure (hardware)
NOTE:
Pressing the Reset button with the Memory Backup Enable jumper pulled performs a COLD Start.
If an external charging source is connected, it must be disconnected. Slide the external battery pack charger, CHGR
INPUT +/- terminal block J17 (see Figure 77:
Battery charger and battery pack connections
on page 84), from the
XRC
G4
board green terminal block.
Disconnect the battery pack connector from the XRC
G4
board BAT CONN connector J16 (see Figure 77.)
Disable memory backup, J1 (see Figure 83) by moving the pin jumper to pins 2 and 3.
Figure 83: Lithium Battery Backup Enable/Disable
To return to service, reconnect the 12 Vdc battery pack connector to the XRC
G4
board BAT CONN connector J16 (see
Figure 77), and observe the LCD.
If removed, reconnect the external battery pack charging source to CHGR INPUT connector J17 (see Figure 77.)
Enter all necessary parameters (go to Section 3.5,
)or send a saved station file (go to Section 2,
main PCCU screen, on the top menu, select
at the bottom of the screen. The Save Station files dialog box displays.
Wait for the backup to complete. Progress status messages display at the bottom of the screen.
When the upload complete message displays, select
to restore (copy) the warm configuration to tfCold
and ensure the configuration files now show in tfCold
).
When
the XRC
G4
has been COLD-started, the 24-hour clock will reset to 00:00:00.
Enable the memory backup J1 (see Figure 83), by moving the pin jumper to pins 1 and 2.