7 - Operation
8. Reactive Power
This section of the menu may be used to manage the supply of reactive
power into the grid. There are 5 possible types of management:
•
Q: No Regulation:
no regulation of reactive power. To activate this
mode, press
ENTER
and then press
ENTER
to confirm.
•
Cos-phi fixed:
Sets the power rating to a fixed value. To activate this
mode, press
ENTER
and set the Cos-Phi value to Over excited or Un-
der excited, from 1.000 to 0.8000; press
ENTER
to confirm.
•
Q Fixed:
Sets the reactive power to a fixed value. To enable this mode,
select
Enable
and then
OK
(using the UP / DOWN arrows). When
enabled,
Set value
will appear on the display, allowing you to set the
value of the reactive power (as either Over or Under excited, from
1.000 to 0.001)
•
Cos-phi = f(P):
Power rating as a function of the active power sup-
plied by the inverter. To enable this mode, select
Enable
and then
OK
(using the UP / DOWN arrows). When it has been enabled,
Load std
curve
will appear on the display, allowing you to set the following con-
trol curve:
Cos-phi (Over excited)
P/Pn
1
0.9
0.85
0.95
0.95
0.85
0.9
0.20
.3
0.4
0.6
Cos-phi (Under excited)
0.50
.7
1
0.9
0.8
•
Q = f(U):
reactive power as a function of the grid voltage measured by
the inverter. To enable this mode, select
Enable
and then
OK
(using the
UP / DOWN arrows). When it has been enabled,
Load std curve
will
appear on the display, allowing you to set the following control curve:
Q/Pn
Vout
0
-0.2
-0.3
-0.36
0.1
-0.1
0.36
0.3
0.2
210
220
230
240
250
The curve can be modified using
the Aurora Manager Lite configu
-
ration software
The curve can be modified using
the Aurora Manager Lite configu
-
ration software