Ex relevant specifications
48 TZIDC-200,
TZIDC-210, TZIDC-220
42/18-85-EN
10 Ex relevant specifications
Change from one to two columns
10.1 TZIDC-200
10.1.1 FM / CSA
FM Approval HLC 8/02 3010829
Explosion Proof; enclosure 4X; T5, max. 82 °C
CL I; Div 1; Grp. C-D
Intrinsic Safety; enclosure 4X; T5, max. 82 °C
CL I, II, III; Div 1; Grp. A-B-C-D-E-F-G
Non-Incendive; enclosure 4X ; T4, max. 85 °C
CL I; Div 2; Grp. A-B-C-D
CL II, III; Div 2; Grp. F-G
Dust-Ignition Proof; enclosure 4X; T5, max. 82 °C
CL II, III; Div 1; Grp. E-F-G
CSA Certification 1393920
Explosion Proof; enclosure 4X; T5, max. 85 °C
CL I; Div 1; Grp. C-D
CL II; Div 1; Grp. E-F-G
CL III
Intrinsic Safety; enclosure 4X; T5, max. 82 °C
CL I; Div 1; Grp. A-B-C-D
CL II; Div 1; Grp. E-F-G
CL III
10.1.2 ATEX / GOST Russia / GOST Ukraine
10.1.2.1 Flameproof enclosure
Designation:
II 2 G Ex d IIC T4/T5/T6
Type Examination Test
Certificate:
DMT 02 ATEX E 029 X
Type:
TZIDC-200 Doc. 901132
Device class:
II 2G
Standards:
EN 60079-0: 2009
EN 60079-1: 2007
Electrical data
Voltage:
≤
30 V AC/DC
Amperage:
≤
20 mA
Pneumatic data
Supply pressure:
≤
6 bar
Thermal data
T4: -40 °C < T
amb
< 85 °C
T5: -40 °C < T
amb
< 80 °C
T6: -40 °C < T
amb
< 65 °C