![ABB TZIDC-200 Скачать руководство пользователя страница 43](http://html.mh-extra.com/html/abb/tzidc-200/tzidc-200_operating-instructions-manual_5476043.webp)
Specifications
42/18-85-EN TZIDC-200,
TZIDC-210, TZIDC-220
43
9.2.6 Transmission data and influences
Output Y1
Increasing:
Increasing output signal 0 ... 100 %
Increasing pressure at output Y1
Decreasing:
Increasing output signal 0 ... 100 %
Decreasing pressure at output Y1
Characteristic deviation
< 0,5 %
Tolerance band
0.3 ... 10 %, adjustable
Dead band
0,1 ... 10 %, adjustable
Resolution (A/D conversion)
> 16000 steps
Sample rate
20 ms
Influence of ambient temperature
< 0.5 % per 10 K
Influence of vibration
< ± 1 % to 10 g and 80 Hz
Seismic requirements
Meets requirements of DIN / IEC 68-3-3 Class III for strong and
strongest earthquakes.
Influence of mounting orientation
Not measurable.
Meets the requirements of the following directives
-
EMC Directive 2014/30/EU
-
EC Directive for CE conformity marking
9.2.7 Environmental
capabilities
Ambient temperature
For operation, storage and transport:
-40 … 85 °C (-40 ... 185 °F)
When using proximity switches
SJ2-S1N (NO):
-25 … 85 °C (-13 ... 185 °F)
Relative humidity
Operational (with closed housing
and air supply switched on):
95 % (annual average),
condensation permissible
Transport and storage:
75 % (annual average), non-
condensing
9.2.8 Housing
Material / Degree of protection
Aluminum, protection class IP 65 (optional IP 66) / NEMA 4X
Surface / Color
Electrostatic dipping varnish with epoxy resin, stove-hardened. Case
varnished black, RAL 9005, matte, housing cover Pantone 420.
Electrical connections
Screw terminals:
Max. 1.0 mm
2
(AWG 17) for options
Max. 2.5 mm
2
(14 AWG) for bus connector
IMPORTANT (NOTE)
Do not expose the terminals to strain.
Four thread combinations for cable entry and pneumatic
connection
- Cable: thread 1/2-14NPT, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread 1/4-18 NPT
- Cable: thread M20 x 1,5, air pipe: thread G 1/4
- Cable: thread G 1/2, air pipe: thread Rc 1/4
(Optional: With cable gland(s) and pipe plugs if necessary)
Weight
3,0 kg (1,36 lb)
Mounting orientation
Any
Dimensions
See "Dimensions"