Ex relevant specifications
42/18-85-EN TZIDC-200,
TZIDC-210, TZIDC-220
57
10.2.2.2 Operation as intrinsically safe equipment
Designation:
II 2 G Ex ia IIC T6 resp. T4 Gb
II 2 G Ex ib IIC T6 resp. T4 Gb
II 3 G Ex ic IIC T6 resp. T4 Gc
Type-Examination Test
Certificate:
TÜV 02 ATEX 1831 X
Type:
TZIDC-210
Standards:
EN 60079-0:2009
EN 60079-11:2007
EN 60079-27:2008
Temperature class
Ambient temperature range
T4
-40 … 85 °C
T5
-40 … 50 °C
T6
1)
-40 … 40 °C
1)
When using the "digital feedback" plug-in module in temperature class T6, the maximum
permissible ambient temperature range is -40 … 35 °C (-40 … 95 °F)
Electrical data for ia/ib/ic for groups IIB/IIC
With the intrinsically safe Ex i IIC
type of ignition protection, only for
connection to a certified FISCO
power supply unit or a barrier, i.e., a
power supply unit with maximum
values according to the following
table:
Signal circuit
(Te11 / -12)
Voltage = 24 V
Current = 250 mA
Output = 1.2 W
Characteristic curve = linear
L
i
< 10 µH
C
i
< 5 nF
With the intrinsically safe Ex i IIC type
of ignition protection, only for
connection to a certified intrinsically
safe circuit with max. values:
Shutdown contact input
(Te85 / -86)
U
i
= 30 V
C
i
= 3.7 nF
L
i
negligibly small
Mechanical digital
feedback
2)
(Terminals 51 / -52
or 41 / -42)
For max. values, see EC type
examination test certificate number
PTB 00 ATEX 2049 X
2)
When using SJ2_S1N (NO) proximity switch, the positioner may only be used at an
ambient temperature range from -25 … 85 °C (-13 … 185 °F).
Change from one to two columns
Special conditions for ATEX, operation as intrinsically safe equipment
• Prior to final installation, the owner must decide how the device is to be used, either
A) as a device featuring the intrinsically safe "Ex i" type of ignition protection, or
B) as a device with the "Ex d" type of ignition protection,
and he/she must mark the selected type of use on the name plate in a permanent manner.
Specific ambient conditions such as chemical corrosion should be taken into account when
affixing the permanent mark. Only the manufacturer may change the selected type of use
following a review.
• Variants with special certification confirming that they meet the requirements for the
"flameproof enclosure" type of ignition protection may not be used as "intrinsically safe", if
they have been previously used as a flameproof type of ignition protection.
Change from one to two columns