Specifications
42/18-85-EN TZIDC-200,
TZIDC-210, TZIDC-220
45
9.3 TZIDC-220
9.3.1 Communication
Specification
FOUNDATION fieldbus, version 1.5
Physical Layer
Model 113, 121 (IEC 61158-2)
Transmission rate
31.25 Kbit/s
Block types
1 AO Function block
1 PID block
1 Resource block
1 Transducer block
1 physical block
Block class
AO block: standard
PID block: enhanced
Resource block: enhanced
Transducer block: custom
Number of linkage objects
22
Device description (DD)
Rev. No. 1 (file name 0201.ffo,
0201.sym)
File
Common file format (file name:
020101.cff)
Max. execution time
AO block: 40 milliseconds
PID block: 50 milliseconds
Supply voltage
Power feed from the fieldbus
9.0 … c 32.0 V DC
Max. permissible voltage
35 V DC
Power consumption
11.5 mA
Current in the event of an
error
15 mA (11.5 mA + 3.5 mA)
FF Certification
Registered with ITK 4.51, Dec.2003
IT Camp. Number IT023200
Device name
ABB TZIDC-200, TZIDC-210,
TZIDC-220-TAG
Dev. ID
0003200028-TZIDC-200, TZIDC-
210, TZIDC-220XXXXXXXXXX
Device address
Between 10 and 247, default
address 23
ATEX certificate for FISCO
Yes
Insensitive to reversed
polarity
Yes
Class
LM profile 32L, 31 PS
Factory default
The positioner is not delivered in an
aligned state. To adjust the
operating range and control
parameters, an automatic
configuration must be run on the
unit. Otherwise, the transducer block
remains in out-of-service mode.
Diagnostic functions
Self-diagnostics for the positioner
hardware and software, valve
diagnostics with enhanced alarm
handling
9.3.2 Device
name
Device name
ABB TZID-C220XXXXXXXXXX
Dev. ID
0X3200028-TZID-C220XXXXXXXXXXX
9.3.3 Output
Range
0 …6 bar (0 … 90 psi)
Air capacity
at 1.4 bar (20 psi)
supply pressure
5.0 kg/h = 3.9 Nm
3
/h=2.3 scfm
at 6 bar (90 psi)
supply pressure
13 kg/h = 10 Nm
3
/h = 6.0 scfm
Output function
For single or double-acting actuators,
air is vented from actuator or actuator
is blocked in case of (electrical) power
failure
Shut-off values
End Position 0 % = 0 ... 45 %
End position 100 % = 55 … 100 %
9.3.4 Travel
Ste
Rotation angle
Used range
25 … 120°
rotary actuators, optionally 270°
25 … 60°
linear actuators
Travel time
prolongation
Setting range
0 ... 200 seconds, separately for each
direction
9.3.5 Air
supply
Instrument air
free of oil, water and dust acc. to
DIN / ISO 8573-1
pollution and oil content according to
Class 3 (purity: max. particle size:
5
µ
m, max. particle density:
5 mg / m
3
; oil content: max.
concentration: 1 mg / m
3
; pressure
dew point: 10 K below operating
temperature
Supply pressure
1.4 ... 6 bar (20 ... 90 psi)
IMPORTANT (NOTE)
Do not exceed the maximum operating pressure of the
actuator!
Air consumption
< 0.1 kg/h / 0.05 scfm (independent
of supply pressure)