Installing and commissioning
41/18-77 EN
Installing and commissioning
15
3.2.3 Mounting the splash guard cap
Screw the splash guard cap delivered with your positioner into the appro-
priate hole in the bottom plate of the case, as seen in the illustration below.
Use a wrench to fasten the cap. Do not use a screw driver!
Make sure that the splash guard cap is always present during operation.
Otherwise, protection class IP65 cannot be ensured.
Caution
Fig. 4
Mounting the splash guard cap