Installation Guide
24/34 94-1100-00002873 A0 EN
│
TruFit
®
Power Distribution Unit
4.9.2.3
Panelboard Terminals
Refer to panelboard manufacturer’s documentation for detailed installation instructions. General
recommendations:
•
Tightening torque for line, neutral and equipment ground terminal
•
Hardware torque values
Refer to circuit breaker documentation for allowable wire temperature rating, wire size and tightening torque.
•
CT wire routing
Every CT has an internal protective resistor which allows for safe voltages across all the CTs even when the
secondary is opened.
The CT Strip Assemblies are designed to sense branch currents from panelboards. The
power wire from each branch circuit breaker will pass through a CT (with 1 turn) on the CT Strip Assembly. A
secondary sensing signal is brought to the PowerView Module via the wire harnesses.
Type and AWG of CT Load Wire: All 8AWG & THHN 6AWG (or Equivalent)
Internal Hex
Hex Size
Lbs-Ins
Min
Max
3/16
108
120
1/4
180
200
5/16
240
275
3/8
330
375
1/2
450
500
Slotted Screw
AWG Wire
Lbs-Ins
Min
Max
14-10
32
35
8
36
40
6-4
41
45
3-2/0
45
50
Screw Size
Torque (In-Lbs)
#4 Steel
16
#10 Plastic
16
#8 Cu/Al/Steel
24
#10-32 Cu/Al/Steel
32
1/4-20 Al/<.150 Thick
Cu
44
1/4-20 .150 Thick Cu
60
5/16-18 Cu/Al/Steel
110
3/8-16 Cu/Al/Steel
220
1/2-13 Cu/Al/Steel
220