Installation Guide
16/34 94-1100-00002873 A0 EN
│
TruFit
®
Power Distribution Unit
If kick plates were provided with your unit, moving the system to location could be a little difficult. Consider
removing the kick plates and then re-installing once unit is in place. NOTE: The solid kick plate option is only
available for applications where the PDU is installed on a computer raised floor with chilled air being fed through
the floor into the PDU for cooling. For all other applications, vented kick plates must be used to ensure adequate
system cooling.
4.6
Checking the supplied parts
4.6.1
Packaging
Your TruFit system is protected by stretch wrap material to protect the system’s heat treated, matte finished,
and powder coated paint against abrasion and vibration during transit. In addition, ABB then protects each of the
four corners with double wall corrugated corner boards which protect the unit during transit.
4.6.2
After Positioning the PDU
−
Verify all items have been received, including spare parts if purchased.
−
Carefully remove the stretch wrap by cutting the material at one of the rear corners of the system.
REMEMBER, this stretch wrap is the final layer of packing material on the system, so be careful in both
cutting and removing the stretch wrap.
−
Verify model numbers match the numbers shown on your order. Model and serial numbers, as well as
rating configuration, are located on the inside front door. Record these numbers in the front of this
installation manual.
−
Open the doors and interior access panels to check for shipping damage. Verify the system’s main circuit
breaker, any secondary main circuit breaker, and all branch circuit breakers are in the “OFF” position prior
to initial system start-up.
−
Check for unsecured components or any loose connections in the cabinet.
−
Check for any unsafe condition that may be a potential safety hazard.
−
Once the inspection has been completed and no problems found, the unit is ready for installation.
Packing material recycling!
ABB, in compliance with environment protection, uses only environmentally friendly
material at the end of its service life, must be recovered conforming to the local
applicable regulations.
PDU packing materials must be recycled in compliance with all applicable regulations.