Storage
4.3.1
Storage of the PDU for Later Commissioning
The equipment is carefully packed for transport and storage so that it is in a
perfect condition when eventually installed.
Never leave a PDU outside the building and do not store the PDU one on top of the
other.
It is advisable to store the PDU in its original package in a
dry, dust-free room, away from chemical substances,
and with a temperature range not exceeding
-13°F
(-25°C) to
131°F
(55°C).
Care must be taken to prevent foreign objects to fall into PDU openings (e.g. debris due to construction works or
fasteners). Do not perform construction work over the PDU cabinet.
Some important functions of the PDU, such as the customized functions, are defined by parameters stored in a
RAM memory
.
A small backup Battery located on the Control Unit board supplies the RAM. If the storage time of the PDU
exceeds
1 year
, these functions
should be verified
by an authorized Service Center before putting the PDU into
operation.
4.4
Place of installation
4.4.1
PDU location
PDU installation and connection must be performed only by an ABB Service
Technician!
If optional cabinets and accessories are included with the PDU, please refer to those
accompanying manuals for installation and operating instructions.
The PDU is intended for use in a restricted-access location only.
Do not locate or stock easily flammable materials in the same room as the PDU.
The PDU is designed for indoor applications only and must be protected from excessive moisture or corrosive
environments. The PDU is not intended for use in the presence of explosive gases.
It is important to have a clean, dust-free environment provided with proper ventilation and air-conditioning to
keep the ambient temperature within the specified operating range.
Required operating environment conditions:
−
Ambient:
32°F to 104°F (0°C to 40°C)
−
Relative humidity: 10 to 95% non-condensing
−
Altitude:
3300 feet (1000 meters)
This unit complies with the limits for a Class A digital device in accordance with Part 15, Subpart J of the FCC
rules; therefore, it is suitable for use in a commercial environment. If not used in accordance with its design
intent, and in accordance with the instructions contained within this manual, PDU may cause interference with
radio frequency communications. If interference is expected, the PDU should be moved away from sensitive
equipment.
Check for
proper floor load capacity
before installing the PDU.