While we are only looking at these two setup configurations within the
confines of this reference guide, additional setup configurations do exist.
Please refer to the LevelMaster User’s Manual for further information.
MasterLink Software
When the equipment configuration does not contain a host unit such as a
XRC or flow computer, MasterLink is the primary tool used for setup and
calibration. MasterLink is a Windows-based program that is designed
specifically for this purpose.
The following procedures assume that MasterLink and the LevelMaster
are installed and power is applied to unit. Additionally, the LevelMaster is
RS-485 only and will need to be converted to RS-232 to communicate
with the laptop computer.
1. Connect the converter cable between the communication ports on
the laptop computer and the LevelMaster communication connector
(see Figure 8).
Level Master Board
P/N 2018546-xxx
Cable Assembly
P/N 2100250-xxx
Cable Assembly
P/N 2100241-xxx
9V
Ba
tt
9V
Ba
tt
B&B Electronics Model # 485SD9TB
Port-Powered RS232/RS-485 Converter
Connect to Computer
COM 1 or 2
Note:
Disconnect red wire connector on
battery assembly when power to the
LevelMaster is turned off. Failure to do so
will result in a constant battery drain.
Figure 8. MasterLink Communication Cable