11
5. In
the
Applications
tab, locate
Application Slot 20
. Click in the
Type
field to open the drop-down menu, and select
LevelMaster
.
6. Click
the
Send
button. The application will load.
7. Locate the LevelMaster application in the tree view, and click on it
(see Figure 13).
Figure 13. Define LevelMaster Application
8. The LevelMaster Setup screen displays. Assign a name in the
Device/APP ID
field and then the number of tanks in the
Value
field.
Click the
Send
button.
9. Return to the tree view and expand the LevelMaster application by
clicking
+
next to
LevelMaster
. The number of tanks set in the
Value
field from the previous step are reflected as individual numbered
entries.
10. In the tree view, expand the Communications entry by clicking
+
next
to
Communications
.
11. Select the
LevelMaster
port, and click on it to open the
Setup
window.
12. Within the
Setup
window, set the values for the
Protocol
(LevelMaster),
Baud Rate
(9600) and
Port Name
. When finished,
click the
Send
button (see Figure 14).
Figure 14. LevelMaster Communication Setup
13. Move to the
Advanced
tab, and set the
Xmit Key Delay
(80ms),
Unkey Delay
(10ms),
Timeout
(8000ms) and Retries (1). When
finished, click the
Send
button (see Figure 15).