Troubleshooting Table
Code Message
Action
0000 No
errors
Float 0 (Top Float)
0001
No ICOMP signal. Detection of
broken primary coil.
The box needs to be tested. If
OPEN, the sensor needs to be
replaced.
0002
V0 through V3 below threshold.
No float or float not recognized or
float battery dead or float
malfunction.
Cycle the power. Float
replacement may be necessary.
0003
V3 is negative and V2 < limit.
Float position out of range.
Cycle the power. Float
replacement may be necessary.
0004
ABS (DIST-long coil) > limit.
Measured distance minus long
coil measurement exceeds
threshold value. Possible broken
or shorted coil.
The box needs to be tested.
0005
Level offset calculation error.
Compensated value below 0 or
above 655.
Temperature
0010
No ICOMP signal. Detection of
broken primary coil.
The box needs to be tested.
0020
Broken secondary wire.
The box needs to be tested.
0030
Analog to digital converter
saturation.
See below.
Float 1 (Bottom Float)
1000
No ICOMP signal. Detection of
broken primary coil.
The box needs to be tested. If
OPEN, the sensor needs to be
replaced.
2000
V0 through V3 below threshold.
No float.
3000
V3 is negative and V2 < limit.
Measured distance minus long
coil measurement exceeds
threshold value.
4000
ABS (DIST-long coil) > limit.
Measured distance minus long
coil measurement exceeds
threshold value. Possible broken
or shorted coil.
5000
Level offset calculation error.
Compensated value below 0 or
above 655.
1011
-1 level reading.
Check the power, interface card,
wiring and protocol settings.