17
5. Set the ohmmeter to the 2K range, and attach the leads to the test
box.
6. Record the readings for future reference.
7. On the backside of the test box is a resistance table for different
windings for each sensor. If the winding readings are +/- 5.0% of the
resistance table on the backside of the test box, the sensor passes
the test. If the test fails, the reading will normally be open or shorted
wires. If this is the case, the sensor will need to be replaced.
8. Disconnect the ribbon cable from the test box cable, and reconnect
the ribbon cable to the interface board.
9. Set the board in the conduit housing, and replace the yellow
fiberglass tension support.
10. Reconnect the green phoenix connector.
11. Replace the Killark conduit dome cover.