8
2. After powering up the laptop, start the MasterLink software program
by clicking the corresponding icon.
3. When the Totalflow MasterLink window appears, select
Setup
Sensor
from the main toolbar. From the drop-down menu, select
Advanced Setup LevelMaster
.
4. In the New LevelMaster Setup window, the user can select one of
two options to set up the LevelMaster (see Figure 9). If there is only
a single LevelMaster to set up, select the first option button calling
for a single set up. If there are several LevelMasters to be daisy-
chained, select the second option button and then enter in an ID for
the first LevelMaster. For simplicity’s sake, increment each ID
number by 1 (i.e., first LevelMaster = 1, second LevelMaster = 2,
etc.). Click the
Setup LevelMaster
button.
5. A dialog box displays asking if the user wants to add the LevelMaster
to their list. Click the
Yes
button.
6. A similar dialog box then displays asking to name the corresponding
LevelMaster. Assign a name to the device, and click the
OK
button.
7. Verify that the LevelMaster was successfully added in the new
screen. A new dialog box will appear asking if the user wants to add
the LevelMaster to their list. Click the
Yes
button.
Figure 9. Initial LevelMaster Setup Screen
8. The user is now returned to the Setup LevelMaster window (see
figure 10). Several tabs are now available. Click the
Setup
tab to
establish the ID and adjust the tank gauge(s). The LevelMaster ID is
a string of numeric characters up to 99. Enter the number, and click