44/78 SUREWAVE SFC USER MANUAL
Terminal no.
Name
Description
P286-A-1
Ready
High signal indicates that system is initialized, ready for
commands
P286-A-2
Running
High signal indicates system is in final running state, on
load and ramps complete,
Signal is low during start-up, shutdown or stopped states
P286-A-3
Warning
High signal indicates a system warning is active.
System will continue to run but investigation is needed.
P286-A-4
Fault
High signal indicates system in fault or trip, or emergency
stop issued. System can only be restarted if fault no longer
present and reset is issued to clear the trip.
P286-B-1
Overload
High signal indicates system is supplying more than over-
load current set point. If this overload persists, the system
will eventually trip after configurable trip time.
P286-B-2
Synchronized
High signal indicates output power terminals are synchro-
nized to external bus.
P286-B-3
Loaded
Only relevant in virtual generator mode. When set high, load
ramp is at 100%, when low, load % is 0 or not yet reached
100%
P286-B-3
Reserved
Table 9-2: Summary of status outputs
9.2.3 Analogue inputs
Four analogue inputs are provided, to enable customer input of setpoints. Depending on the
output mode selected by the operator, one or more of these setpoints may be used to control
the operation of the SFC. Alternatively, fixed setpoints as entered into the GDM may be used.
The source for each setpoint may be individually configured from the GDM.
Table 9-3 summarizes these analogue inputs. Two inputs are for +/-10V and the other two are
for 0-20mA or 4-20mA.
Figure 9-6: User analogue inputs