Table 11.2.2.8.-1 Measured value (MV) (Continued)
MV class
Attribute
Name
Attribute Type
FC
TrgOp
Value/ Value
range
M/O/C
SPA-ZC 400/
Comments
q
Quality
MX
qchg
M
Supported
t
TimeStamp
MX
M
Supported
Substitution
subEna
BOOLEAN
SV
PICS_SUBST Not Supported
subVal
AnalogueValue
SV
PICS_SUBST Not Supported
subQ
Quality
SV
PICS_SUBST Not Supported
subID
VISIBLE
STRING64
SV
PICS_SUBST Not Supported
Configuration, Description and Extension
units
Unit
CF
see Annex A
O
Supported
db
INT32U
CF
0...100 000
O
Not Supported
zeroDb
INT32U
CF
0...100 000
O
Not Supported
sVC
ScaledValue-
Config
CF
AC_SCAV
Not Supported
rangeC
RangeConfig
CF
GC_CON
Not Supported
smpRate
INT32U
CF
O
Not Supported
d
VISIBLE
STRING255
DC
Text
O
Supported
cdcNs
VISIBLE
STRING255
EX
AC_DLNDA_M Not Supported
cdcName
VISIBLE
STRING255
EX
AC_DLNDA_M Not Supported
dataNs
VISIBLE
STRING255
EX
AC_DLN_M
Not Supported
Different variants of the type exist based on the connectivity
package short address information (sAddr). Underlined
information indicates the basic type.
11.2.2.9.
Complex measured value (CMV)
Table 11.2.2.9.-1 defines the common data class of measured value.
86
SPA-ZC 400
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1MRS755347
Содержание SPA-ZC 400
Страница 1: ...Ethernet Adapter SPA ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 22: ...22 ...
Страница 30: ...30 ...
Страница 60: ...60 ...
Страница 72: ...72 ...
Страница 74: ...74 ...
Страница 112: ...112 ...
Страница 114: ...114 ...
Страница 116: ...116 ...
Страница 118: ...118 ...
Страница 120: ......
Страница 121: ......