Prefix, InClass and InInst define the object tree's caption. Caption is shown in
the following way: I InInst = LN Caption.
6.6.
Configuring by using imported CID file
If you have to configure several SPA-ZC 400 with the similar IEC 61850 data
object model, it is possible to import a previously generated CID file and
change the communication addresses, typically by changing the IP address.
1. Create the project and add the logical device LD0 like in
Section 6.4. Building object tree.
2. Add a logical device to the SPA-ZC 40x Device object by right-clicking to
select
SPA-ZC 40x > New > Communication > Logical Device
.
3. Select the CID import function by choosing a new empty logical node and
then right-click to select the CID import function.
In the CID import dialog you can select the right CID file from the
workstation directory and import it to a previously created logical node. LD0
contains the data sets and reporting control blocks. Other logical devices
describe the data model of a connected IED.
6.7.
Configuring communication parameters
SPA-ZC 400 communication parameters are located in the device properties.
SPA-ZC 400 uses static IP addresses, which have to be defined in the planned
network structure.
*
IP Address
IP address identifies SPA-ZC 400 in Local Area Network (LAN). All
communication via SPA-ZC 400 uses this address. The default value is
192.168.2.10 and it has to be changed to a unique address according to the
planned network structure.
*
Default Gateway
This IP address defines the gateway's address, which forwards IP traffic
between the local subnet and outside world. The default value is
192.168.2.1 and it has to be changed according to the planned network
structure.
*
Subnet Mask
This subnet mask defines which addresses are not in the local subnet and
must be accessed through the default gateway.
*
SNTP Servers
SPA-ZC 400 uses SNTP for its own realtime clock. Time is used for
synchronizing IED with SPA time synchronization. One SNTP Server has
to exist in the accessible network, otherwise SPA-ZC 400 event time
stamping is not working properly. The primary server is mainly in use.
The secondary SNTP server is used if the primary SNTP server cannot be
40
SPA-ZC 400
Ethernet Adapter
SPA to IEC 61850 Gateway
Installation and Commissioning Manual
1MRS755347
Содержание SPA-ZC 400
Страница 1: ...Ethernet Adapter SPA ZC 400 SPA to IEC 61850 Gateway Installation and Commissioning Manual ...
Страница 2: ......
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 22: ...22 ...
Страница 30: ...30 ...
Страница 60: ...60 ...
Страница 72: ...72 ...
Страница 74: ...74 ...
Страница 112: ...112 ...
Страница 114: ...114 ...
Страница 116: ...116 ...
Страница 118: ...118 ...
Страница 120: ......
Страница 121: ......