KNX control elements and application parameters
"Switch" control element
Product manual 2CKA001473B5343
│
117
–
Pressing/releasing
: Pressing = value 1; releasing = value 2.
The following supplementary parameters are available, see chapter “Object type 1 / value 2“
on page 117:
–
Object type value 1
: When actuated (pressing) the control element sends telegrams via
the associated communication object. This parameter is used to specify the size of the
communication object.
–
Object type value 2
: When actuated (releasing) the control element sends telegrams via
the associated communication object. This parameter is used to specify the size of the
communication object.
–
Short/long
: Short press = value 1; long press = value 2.
The following supplementary parameters are available, see chapter “Object type 1 / value 2“
on page 117:
–
Long operation after...
:
Options:
Setting option from 0.3 - 10 seconds
The parameter is used to specify how long the button must be pressed to recognize a
long operation.
–
Object type value 1
: When actuated (short press) the control element sends telegrams
via the associated communication object. This parameter is used to specify the size of
the communication object.
–
Object type value 2
: When actuated (long press) the control element sends telegrams
via the associated communication object. This parameter is used to specify the size of
the communication object.
10.1.6 Object type 1 / value 2
Options: Inactiv
Switch
Forced
operation
1-byte value [0% - 100%]
1-byte value [0 - 255]
1-byte value [-128 - 127]
Scene
number
RTC
operating
mode
Temperature
2-byte value [-32768 - +32767]
2-byte value [0 - 65535]
2-byte
floating
point
4-byte value [-2147483648 - 2147483647]
4-byte value [0 - 4294967295]
14-byte text
Parameters "Object type value 1" and "Object type value 2" are used to specify the size of the
communication object.
Notice
The parameters are only available when parameter "Type of switching" is set on
"Pressing/releasing" or "Short/long".
Содержание SmartTouch B/stainless
Страница 57: ...Commissioning via ABB free home Product manual 2CKA001473B5343 57 ...
Страница 59: ...Commissioning via ABB free home Product manual 2CKA001473B5343 59 Abb 33 Other settings Part 2 ...
Страница 84: ...Commissioning of the KNX function via ABB DCA SmartTouch 10 from ETS5 Product manual 2CKA001473B5343 84 ...
Страница 121: ...KNX control elements and application parameters Switch control element Product manual 2CKA001473B5343 121 ...
Страница 302: ...KNX communication objects Application Internal RTC Product manual 2CKA001473B5343 302 Pa ...
Страница 309: ...Operation Product manual 2CKA001473B5343 309 12 2 2 Additional basic principles Fig 46 Basic principles ...