KNX control elements and application parameters
Control element: "Value slider"
Product manual 2CKA001473B5343
│
168
The parameter is used to enter the unit or the unit sign with which the value is displayed in
the control element.
The length is limited to 20 characters.
Decimal places
:
Options:
Setting option from 0 - 2
The parameter is used to specify the number of decimal places of the displayed value.
The number is limited to 2 places.
10.12.6 Slider sends
Options:
When releasing the slider
Cyclic
The parameter is used to specify whether the signal is sent "When releasing the slider" or
"Cyclic".
–
When releasing the slider
: No additional parameters available.
–
Cyclic
: The following supplementary parameter is available:
Telegram is repeated every [sec.]:
Options:
Setting option from 0.25 - 1.25 seconds
The parameter is used to specify the space of time between two value telegrams.
10.12.7 Object type
Options:
1-byte value [0% - 100%]
1-byte value [0 - 255]
1-byte value [-128 - +127]
2-byte value [0 - 65535]
2-byte value [-32768 - +32767]
2-byte
floating
point
4-byte value [0 - 4294967295]
4-byte value [-2147483648 - 2147483647]
4-byte
floating
point
When actuated, the control element can send telegrams via the associated communication
object.
Parameter "Object type" is used to specify the size of the communication object.
–
1-byte value [0% - 100%]
: A value is sent as 1-byte value without a sign (percentage value).
–
1-byte value [0 - 255]
: A value is sent as 1-byte value without a sign, e.g. actuating value,
angle or brightness value.
–
1-byte value [-128 - 127]
: A value is sent as 1-byte value with a sign, e.g. actuating value.
–
2-byte value [0 - 65535]
: A value is sent as 2-byte value without a sign, e.g. actuating value
or time interval.
–
2-byte value [-32768 - +32767]
: A value is sent as 2-byte value with a sign, e.g. actuating
value or time difference.
–
2-byte floating point
: A value is sent as 2-byte floating point value, e.g. a temperature value,
a time duration, a power or a consumption value.
Содержание SmartTouch B/stainless
Страница 57: ...Commissioning via ABB free home Product manual 2CKA001473B5343 57 ...
Страница 59: ...Commissioning via ABB free home Product manual 2CKA001473B5343 59 Abb 33 Other settings Part 2 ...
Страница 84: ...Commissioning of the KNX function via ABB DCA SmartTouch 10 from ETS5 Product manual 2CKA001473B5343 84 ...
Страница 121: ...KNX control elements and application parameters Switch control element Product manual 2CKA001473B5343 121 ...
Страница 302: ...KNX communication objects Application Internal RTC Product manual 2CKA001473B5343 302 Pa ...
Страница 309: ...Operation Product manual 2CKA001473B5343 309 12 2 2 Additional basic principles Fig 46 Basic principles ...