IDDERO HCx-KNX TOUCH PANELS 

 

User Guide 

 

Summary of Contents for HC -KNX Series

Page 1: ...www iddero com 130122 02 IDDERO HCx KNX TOUCH PANELS User Guide ...

Page 2: ... 1 Scenes 21 4 2 Time Schedules 22 4 3 Alarms 23 4 4 Presence Simulation 25 4 5 Logic Functions 26 4 6 Video Door Phone Function 30 4 7 IP Cameras 30 4 8 E mail 30 4 9 GSM Module 31 4 10 Internal Thermostat 31 4 11 Date and Time 32 4 12 Web Access 33 5 CONFIGURATION SOFTWARE 36 5 1 Introduction 36 5 2 Overview 36 5 3 Menus 37 5 4 Project Tree 39 5 5 Communication Objects 39 5 6 Address Tree 40 201...

Page 3: ...ring This manual is intended for installers and system integrators and provides technical information about the operation and configuration of Iddero touch panels 2 OVERVIEW 2 1 System Components Iddero touch panels are wall mounted units that can be conveniently and intuitively controlled through their colour touch screen 1 The unit features a LED status indicator 2 which provides immediate visua...

Page 4: ...ouch panels is designed to be conveniently operated without the need of external devices such as a stylus Simply touch with your finger on the graphical representation of buttons icons or any other element you want to activate User Interface Elements The following screenshot shows the main elements of the user interface 2 1 4 3 ...

Page 5: ...one call in progress The central area of the screen 2 shows different icons buttons and additional items that you can use control the system At the bottom of the screen the navigation bar 3 allows you to move quickly between different pages linked to a particular zone see Chapter 3 User Interface The Back icon 4 allows you to return to the previous page or section at any time 2 3 Install Mode Ente...

Page 6: ...P address is 192 168 0 200 with subnet mask 255 255 255 0 default values the IP address of the PC should also be in the 192 168 0 x range for example 192 168 0 201 with subnet mask 255 255 255 0 The current IP address and subnet mask of the touch panel are shown on the installation screen Please refer to your operating system s documentation for detailed help on configuring the network settings on...

Page 7: ...dules Security Alarm log Edit time schedules Power saving mode Inactivity time Inactivity time Incoming call System idle Boot Touch Once the system starts up the home page is automatically shown This page can display a configurable logo if not customized the Iddero logo is shown by default Control pages are configurable pages that allow for control and monitoring of the devices and appliances in t...

Page 8: ...tion frequency of use of the devices etc Each zone can consist of up to eight control pages and each control page can group up to eight devices Therefore up to 64 devices are allowed per zone Zone Selection Zone selection can be done through maps which are often used to graphically represent the home or building plan A series of active areas or touch areas is defined in each map Each touch area ca...

Page 9: ...ber of devices that can be displayed on a control page depends on the layout that was configured for that page The following figure shows the available layouts There are eight generic layouts plus one specific layout for HVAC control pages 1x1 2x1 1x2 2x2 1x3 2x3 1x4 2x4 HVAC ...

Page 10: ...ess and long press Send a user selected value out of several available options up to four options can be configured per button Regulation bar A generic component that displays and sends values to a communication object through an interactive regulation bar This component can be used with numeric data types Numeric keypad A generic component that displays and sends values to a communication object ...

Page 11: ...ontrol pages specifically designed to monitor and control HVAC equipment For each HVAC page the HVAC system type to be controlled must be configured The following options are available Standard thermostat Designed for control of a standard KNX thermostat Thermostat control can be done by temperature setpoint and or by thermostat mode Control by thermostat mode allows setting of the current thermos...

Page 12: ...hown Provides access to the security page If no security functions alarms or presence simulation have been configured this button will not be shown Provides access to the time schedules page If no time schedule channels have been configured this button will not be shown Provides access to the user preferences and settings pages 3 4 Time Schedules The time schedules page shows a list of the existin...

Page 13: ...s when a guest presses the call button in the door phone station the touch panel will play a ring tone through the integrated loudspeakers and the incoming call icon will be shown in the status bar If the touch panel was idle it will automatically turn on and switch to the video door phone page If the option Password required to start session has been enabled for the project see Section 3 9 Access...

Page 14: ...alog Checking the Door without an Incoming Call You can navigate to the video door phone page at any time even if there is no incoming call You will be able to watch the video captured by the door phone s camera but will not be able to establish an audio communication Depending on the door station type and configuration the open door buttons may not be available if there is no call in progress Aud...

Page 15: ...itch between door stations an informative message will be briefly shown onscreen when you enter the video door phone page The pick up hang up buttons always relate to the current call in progress regardless of which door station is currently selected The door opening buttons always relate to the door station currently selected They may or may not be shown depending on the configuration of the sele...

Page 16: ...ameras page lists all IP cameras configured in the project Select any of the available cameras to get a live preview of the video captured by the camera Touch the preview image to switch to full screen mode Once in full screen mode touch anywhere on the screen to go back to the cameras page ...

Page 17: ...ters Recalibrate touch Clean screen Date time Passwords Network config Web server Video door phone IP cameras Initial settings Reboot system E mail User Interface This section provides the following options Language Allows selection of the user interface language English Spanish German French Portuguese or Catalan Buzzer By default the screen will beep when the user touches a user interface elemen...

Page 18: ...Configure which actuators will be involved in the presence simulation during the day and night periods out of the available actuators that have been enabled in the project for the presence simulation function Scenes This page allows end users to configure the name of each scene defined in the project If the Scenes as Sequences of Actions model has been selected see functional description in Chapte...

Page 19: ... you will need to select one before proceeding Available parameters will depend on the door phone type and configuration For more information please refer to the application notes on video door phone configuration available in the download area of the Iddero website IP cameras A list of IP cameras defined in the project will be displayed Select any camera to edit its configuration parameters IP ad...

Page 20: ... be required Current user permissions remain in effect until the user returns to the home page either manually or due to system idle time see next section 3 10 System Inactivity and Power Saving Mode After a certain period of inactivity i e no user interaction the system automatically returns to the home page Once on the home page and again after a certain period of inactivity the system enters po...

Page 21: ... save the current values and states of the actuators involved For example let s assume we want to modify the above mentioned Movies scene so that the light level is set to 25 instead of 40 We would proceed as follows 1 Activate the Movies scene The light level is set to 40 2 Manually set the light level to 25 3 Save the scene The scene will internally be updated to use the new values Similarly to ...

Page 22: ... s assume that the Activation by telegram and Save by telegram options are enabled in the project and there is a scene with 15 as scene identifier To activate the scene by external telegram a 1 byte telegram with value 15 must be sent to the Recall save scene communication object To save the scene by external telegram a 1 byte telegram with value 143 143 15 128 must be sent to the Recall save scen...

Page 23: ...at 03 00am even though Saturday was not included in the Week days field This is because the week days and date range checks are always done for the start action and the result of these validity checks is automatically applied to the end action as well On the other hand note that if the start time is set to 03 00 and the end time to 22 00 both actions will be run on the same day Friday Each timer c...

Page 24: ... still active The following flowchart shows the possible transitions between states Detailed explanation Initially all alarms are in idle state Inactive When the alarm condition is activated a telegram with the activation value is received in the corresponding communication object the alarm switches to Active state If an alarm is active and the alarm condition deactivates it switches to Waiting fo...

Page 25: ...ng events are logged System startup Alarm activation Alarm acknowledgment for alarms requiring acknowledgment Alarm deactivation for alarms not requiring acknowledgment Enabling and disabling the bypass function Enabling and disabling presence simulation Clearing the alarm log 4 4 Presence Simulation The presence simulation function performs different actions on a set of devices and appliances thu...

Page 26: ...re combined to implement a more complex function it will not be necessary to send intermediate values to the KNX bus In this case the so called internal group addresses are frequently used As the name suggests these addresses are internal to the system and consequently do not generate any traffic on the KNX bus Logic functions also support an optional disabling object This is a 1 bit communication...

Page 27: ...NOR XNOR 0 0 0 0 0 1 1 1 0 1 0 1 1 1 0 0 1 0 0 1 0 1 0 1 1 1 1 1 1 0 0 0 Three input gates I1 I2 I3 AND OR XOR NAND NOR XNOR 0 0 0 0 0 0 1 0 1 0 0 1 0 1 1 1 1 0 0 1 0 0 1 1 1 1 0 0 1 1 0 1 0 1 1 1 1 0 0 0 1 1 1 1 0 1 0 1 0 1 0 1 1 1 1 1 0 0 1 0 1 1 1 1 1 1 1 1 1 0 1 0 Four input gates I1 I2 I3 I4 AND OR XOR NAND NOR XNOR 0 0 0 0 0 0 0 1 1 1 0 0 0 1 0 1 1 1 0 0 0 0 1 0 0 1 1 1 0 0 0 0 1 1 0 1 0 1 0...

Page 28: ...1 byte objects etc Multiplexers and demultiplexers can be 2 channel or 4 channel devices The control signal consists of a 1 bit object for 2 channel devices and of two 1 bit objects for 4 channel devices The following logic tables show the operation of multiplexers and demultiplexers in detail Ix Input x Cy Control object y Qz Output z MUX2 MUX4 DEMUX2 DEMUX4 C Function C1 C2 Function C Function C...

Page 29: ...rresponding value will be sent out Otherwise the Transmit when function re enabled parameter will determine whether the last value that was generated before disabling should be retransmitted Comparators Comparators are elements that compare two numeric values at their inputs A and B and update their binary output depending on the result of the operation The actual condition to check can be configu...

Page 30: ...rmation about video door phone monitoring on Iddero touch panels 4 7 IP Cameras Iddero HC2 KNX and HC2L KNX touch panels enable real time monitoring of IP cameras in the home or building Available IP cameras can be defined during at project configuration time Predefined camera models can be added by simply selecting the manufacturer and part number Additionally generic cameras can also be configur...

Page 31: ...tat Besides being able to control any KNX thermostat in the installation Iddero touch panels also implement an internal thermostat function This thermostat function can be used with the integrated temperature sensor HC1 KNX model with the DW TS N1P external temperature probe HC2 KNX and HC2L KNX models or with any temperature measured by an external KNX device General Operation The internal thermo...

Page 32: ...e correction factor during this period of time if the user tries to modify the correction factor during this period the system will pop up a warning message but will allow the user to proceed if they wish to do so This stabilization period is only applicable to the HC1 KNX panel and only if the thermostat function is configured to use the integrated temperature sensor 4 11 Date and Time Iddero tou...

Page 33: ...ring of devices time schedules scenes etc Initial Configuration No special configuration is required in order to use the integrated web server However for convenience the configuration software allows to specify whether the web server will be initially enabled as well as the default values for user name and access password by means of the following configuration options General section Option Defa...

Page 34: ...interface is functionally equivalent to the local user interface of the touch panel itself The exact layout of the visualization is adapted to the screen size and browser type of the client device Any access levels defined in the project are also honoured Access restrictions work just the same as when working directly with the touch panel Users can browse through all sections and pages that have b...

Page 35: ...www iddero com IDDERO HCx KNX TOUCH PANELS User Guide 35 ...

Page 36: ...tomation installation the navigation between the different available functions and the detailed parameters of system operation 5 2 Overview The following figure shows the main application window The top area of the application window shows the menu bar along with a toolbar containing buttons for quick access to some of the available menu actions The main area of the window is split in three differ...

Page 37: ...ddresses All the addresses in the project as well as any associations with communication objects will be discarded and all the addresses included in the esf file will be imported The Resource monitor command shows the list of resources currently in use in the project maps zones pages scenes time schedules logic gates etc and resource limits maximum number of items allowed for each type of resource...

Page 38: ...he project for example if you have deleted or added scenes timer channels alarms presence simulation actuators etc The Update firmware command updates the touch panel firmware In order to do this you need to select a valid firmware update file Use only firmware updates released by Iddero Again it is critical not to interrupt the operation or turn off the touch panel during the update process as if...

Page 39: ... remove and select the Delete option from the pop up menu Alternatively you can select the item in the project tree left click and press the Delete key You can also add or delete items in these sections through the list displayed in the parameter area when the section is selected in the project tree The position of some items within the project tree can be changed e g zones pages components To do ...

Page 40: ...ects of the touch panel together in those cases where it is not necessary to send the generated telegrams to the KNX bus You can add edit and delete group addresses in the address tree in the same way as described above for project tree items When you select a group address all communication objects currently associated with that group address are displayed in the parameter area To link a group ad...