ScreenMaster RVG200
Paperless recorder
7 Configuration
74
OI/RVG200-EN
7.7.5 Security
Note.
User 1 is the System Administrator and is able to change the Security type and all other security
parameters. Other users can change only the
Logging security
setting and only if
Security system
is set to
Basic
.
Security
Security type
Set the Security type.
Security system
Select
Basic
or
Advanced
security – see Section 7.2, page 59.
Configuration security
Set the method of access to the
Configuration
level.
If
Password protected
is selected, access is via the password set
for the user – see Section 7.7.6, page 76.
If
Switch protected
is selected, access to the
Configuration
level is
prohibited for all users once the changes have been saved and
made active. Access to the
Configuration
level is then achieved
only by setting the internal security switch to the 'Configuration
level not protected' position – see Fig. 7.3, page 62.
Security Options
Note.
Displayed only if
Security system
is set to
Advanced
.
Logging security
When set to
On
, access to the
Logging
level is protected by each user's
unique password.
Acknowledge security
When set to
On
, each user must enter their unique password in order to
acknowledge alarms.
Logging security
Note.
Displayed only if
Security system
is set to
Basic
.
When set to
On
, access to the
Logging
level is protected by a single,
4-digit password for all users.
Logging password
Note.
Displayed only if
Security system
is set to
Basic
and
Logging
security
is set to
On
.
Enter the password to be used by all users to access the
Logging
level.