ScreenMaster RVG200
Paperless recorder
5 Logging
52
OI/RVG200-EN
5.2 Logging menu
Touch to display the Operator menu.
Logging
Touch to display the sub-menu.
Online
Note.
Greyed-out if no archive media is inserted
or
Archive Media
is set to
None
or
the recorder has been placed in
historical review mode (see page 40).
Logging is off-line. Touch to set logging on-line and start the archiving
process.
When external archive media is inserted, a dialog is displayed giving the User
the option of setting logging on-line and starting the archiving process or
remaining off-line. If no action is taken within 10 seconds, logging is set
on-line and archiving is started automatically.
If the
Archive all Historical Data
checkbox is de-selected, older unarchived
data remains in the internal memory buffer until overwritten by newer data but
is not available for archiving unless 'Reset archiving' (see page 53) is
selected.
Offline
Note.
Greyed-out if the recorder has been placed in historical review mode.
Logging is on-line. Touch to set logging off-line and stop the archiving
process.
Recording of channel data into internal memory continues uninterrupted but
archiving to the selected storage media is suspended until logging is set
on-line again.
Note.
Always set logging off-line before changing the storage media type
selection (see Section 7.7.2, page 70) or removing external media. A
warning is displayed if the storage media type selection is changed or
external media is removed before logging is set off-line.
When logging is set off-line, an
Updating archiving
progress bar is
displayed. Do not remove external media until archiving is complete.
To stop archiving, touch
Stop Immediately
.
Select Line Status
Archive all Historical Data
External Media Inserted.
Press Enter to 'Go Online'
Press Cancel to 'Stay Offline'.
If no action taken, Archiving
will Go Online in 8 secs.