ScreenMaster RVG200
Paperless recorder
4 Operation
42
OI/RVG200-EN
Screen Interval
Chart views only
Note.
Greyed-out if the
Screen interval select
menu enable is not selected
Touch to change the amount of data displayed on the screen. A longer
screen interval displays more data, a shorter screen interval displays data
over a shorter time period, but in more detail. In both cases, the full trace is
preserved by plotting the maximum and minimum samples for each display
point.
The screen intervals available in the menu are determined by the faster of
the primary and secondary sample rates set for the process group during
configuration – see Section 7.8.1, page 80.
Table 4.1 shows the relationship between sample rate and screen interval
for the vertical and horizontal chart views.
Note.
A 'Please Wait' message appears in the status bar while the recorder
retrieves data from storage.
Selecting a different screen interval does not affect the rate at which
data is sampled.
When in historical review mode, changing the screen interval causes
the time at the cursor position to change.
Maximum screen interval
Sample rate setting
Vertical chart view
Horizontal chart view
<1 second
Up to 1 hour / screen
Up to 1.5 hours / screen
More than 1 second, less than 4 seconds
Up to 12 hours / screen
Up to 21 hours / screen
More than 4 seconds, less than 8 seconds
Up to 1 days / screen
Up to 1.5 days / screen
More than 8 seconds, less than 12 seconds
Up to 2 days / screen
Up to 3 days / screen
More than 12 seconds, less than 28 seconds
Up to 3 days / screen
Up to 4.5 days / screen
More than 28 seconds
Up to 7 days / screen
Up to 12 days / screen
Table 4.1 Sample rates and screen intervals