BUSCH-/ABB-SECURE@HOME
2CSM600727D0901
50/74
12.2.3.1
Parameters for detectors
The table lists the possible parameters shared by the various detectors. The additional
specific parameters for a type of detector are shown in the manual for that detector.
Parameter
Meaning
Possible values
Label
Serves to better identify the detector. A descriptive and unique
name is recommended, e.g. KITCHEN, LIVING ROOM, BATHROOM,
PORCH etc.
Alphanumerical characters,
maximum length 10
characters.
Exclude
Exclude the detector (the central unit will ignore any of its alarm
reports), while maintaining the configuration. Corresponds to
the Isolation function, as defined in the EN 50131-1 standard.
YES, NO
Supervision
Select the frequency at which the central unit states that the
detector functions.
NO, 15, 45 (1)
Delay (2)
Delay time between alarm system arming and activation of alarms
when leaving the protected areas, or delay time between intrusion
detection and alarm reports when a protected area is entered.
Allows you to leave the protected areas after arming the alarm
using a command device without triggering the report or to enter
the protected areas and disarm the alarm system located within
those areas. The entry delay time must only be applied to
detectors that cover the route between the entry point (door,
garage shutter, etc.) and the command device.
If different values are set on multiple sensors, the exit delay time
applied is the highest of these values within a single zone. At the
entrance, the time set on the sensor that gener-ates the intrusion
alarm is applied. If there are one or more delayed sensors, after the
alarm has been activated, the
icon appears at the top right of
the display, for the duration of the exit time.
NO, 15, 30, 60, 90. If NO is
selected, the alarm report
is immediate.
(2)
The underlined values are the factory settings.
(1) Frequencies other than 15 minutes do not comply with regulation 50131-6 par. 4.5.1.
(2) Settings based on time delays other than 0 do not comply with the EN 50131-1 and EN 50131-3 regulations.
(3) Subsequent amendments to parameters outside of this interval are stored on the control panel and
received by the detector when the first useful transmission is performed: notification of this situation is
provided via the icon in the top right of the display.