Figure 24: TS side of the optical transceivers with the LEDs D2.1 to D2.4 and D9.1
to D9.4
7.2.3.1
Description of LED HMI functionality
On the top-plate of each SAM600 module, there are three status LEDs which have
a fixed function and cannot be configured.
The function of each LED is as follows:
The green LED (READY) indicates the health status of a SAM600 module.
The yellow LED (WARNING) indicates any warning caused by an issue
related to a SAM600 module.
The red LED (ALARM) indicates severe hardware failure or software
malfunction of the SAM600 module.
Table 13: LED status
Function
Green LED (Ready)
Yellow LED (Warning)
Red LED (Alarm)
Power down
No warning
No alarm
Module is in Bootloader (all LEDs steady light)
Module is operating
normally with a valid
configuration
Module is missing a
sample stream for
merging
Module’s board
temperature
exceeds threshold
Module A/D
calibration integrity
check failed
SAM600 system bus
single link failure
Communication error
in the SAM600
module chain
Module’s digital input
HW error
Module software
failure
SAM600 application
disabled
SAM600 system bus
double link failure
Module is starting
up
Module operates
normally and waits
to receive a
configuration
Simulation mode
activated
Module’s time
synchronization is not as
configured
lists the LED HMI definitions applicable optical transceiver states.
= No indication
= Flash
= Steady light