Section 5
1MRK 511 434-UEN A
SAM600 System Startup
46
SAM600 Process Bus I/O System
Operation Manual
The SAM600 modules in a SAM600 system can be powered on in arbitrary order.
The SAM600 modules will synchronize and automatically detect IEC/UCA 61850-
9-2LE sampled value streams on the SAM600 system bus. If a valid configuration
is available, the SAM600 module starts sampling the analog input values and
publishes IEC/UCA 61850-9-2LE sampled value streams according to its
configuration.
During 60 seconds after initialization the sample quality of the
locally measured quantity (current or voltage) is forced to
Invalid
(0x0001).