Section 2
1MRK 511 434-UEN A
SAM600 Process Bus I/O System
10
SAM600 Process Bus I/O System
Operation Manual
All access points can (externally) receive and publish IEC/UCA 61850-9-2LE
streams from and to the SAM600 system to bay level protection and control
devices.
A SAM600-TS module is optional in a SAM600 system. Up to three SAM600-
TS modules can be chained into a SAM600 system.
Connectors X106 and X107 on the SAM600-TS module can not be
used for SAM600 system bus connection. These two connectors can
only be configured as IEC 61850 access points.