Communication
70
Instance 0x01 attributes
ID#
Attribute
name
Services Description
Data type
0x03 Run 1
1)
Get/Set
0 = Stop, 1 = Run
BOOL
0x04 Run 1
2)
Get/Set
0 = Stop, 1 = Run
BOOL
0x05 Net Control
2)
Get/Set
0 = Local Control,
1 = Network Control
BOOL
0x06 State
Get
1 = Start/up
2 = Not ready
3 = Ready
4 = Enabled
5 = Stopping
6 = FaultStop
7 = Faulted
UINT8
0x07 Running 1
3)
Get
0 = Stopped,
1 = Running
BOOL
0x08 Running 1
4)
Get
0 = Stopped,
1 = Running
BOOL
0x09 Ready
Get
1 = Ready, Enabled or Stopping 0 =
Other state
BOOL
0x0A Faulted
Get
0 = Not faulted,
1 = Fault occurred
BOOL
0x0B Warning
Get
0 = No Warnings present,
1 = Warning
BOOL
0x0C FaultRst
Get/Set
0
!
1 Fault Reset
BOOL
0x0D Fault Code
Get
The fault that caused the last transi-
tion to the Faulted state.
UINT16
0x0F CtrlFromNet
Get
0 = NetControl disabled,
1 = NetControl enabled
BOOL
0x11 Force Fault
Get/Set
0
!
1 Force a fault
BOOL
0x12 Force Status
Get
0 = Not Forced Non-zero = Forced
BOOL
Содержание RETA-01
Страница 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 01 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 10: ...Table of Contents 10 ...
Страница 14: ...Introduction 14 ...
Страница 28: ...Quick start up guide 28 ...
Страница 30: ...Mechanical installation 30 ...
Страница 32: ...Electrical installation 32 ...
Страница 40: ...Drive configuration 40 ...
Страница 80: ...Communication 80 ...
Страница 82: ...Fault tracing 82 ...
Страница 85: ......