Communication
54
Exception codes
The RETA-01 supports the Modbus exception codes shown
below.
Table 13. Supported exception codes
Function codes
The RETA-01 supports the Modbus function codes shown below.
Table 14. Supported function codes
Exception
code
Name
Description
01
Illegal func-
tion
Unsupported command
02
Illegal data
address
Address does not exist or is read/write-pro-
tected
03
Illegal data
value
Value is outside minimum and maximum
limits. Parameter is read-only
Function
code
Name
Description
Modbus
class
03
Read hold-
ing registers
Reads the binary contents of the
holding registers (4X references)
in the slave.
0
06
Preset sin-
gle register
Presets a value into a single hold-
ing register (4X reference).
1
16 (10h)
Preset multi-
ple registers
Presets values into a sequence of
holding registers (4X references).
0
23 (17h)
Read/Write
registers
Performs a combination of one
read and one write operation in a
single Modbus transaction. The
function first reads a group of
4XXXX registers and then writes
new contents to a another group
of 4XXXX registers.
2
Содержание RETA-01
Страница 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 01 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 10: ...Table of Contents 10 ...
Страница 14: ...Introduction 14 ...
Страница 28: ...Quick start up guide 28 ...
Страница 30: ...Mechanical installation 30 ...
Страница 32: ...Electrical installation 32 ...
Страница 40: ...Drive configuration 40 ...
Страница 80: ...Communication 80 ...
Страница 82: ...Fault tracing 82 ...
Страница 85: ......