Communication
58
Extended Speed Control assembly
The Extended Speed Control assembly is defined by ODVA
AC/DC Drive Profile. The format of the output assembly is:
The format of the input assembly is:
Instance 21
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
NetRef
NetCtrl
Fault
reset
Run
reverse
Run for-
ward
1
2
Speed reference (Low byte)
3
Speed reference (High byte)
Instance 71
Byte Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
0
At refer-
ence
Ref
From
Net
Ctrl
From
Net
Ready
Run-
ning
reverse
Run-
ning for-
ward
Warning Faulted
1
Drive state
2
Speed actual value (Low byte)
3
Speed actual value (High byte)
Содержание RETA-01
Страница 1: ...ABB Drives User s Manual Ethernet Adapter Module RETA 01 ...
Страница 2: ......
Страница 4: ......
Страница 6: ...Safety instructions 6 ...
Страница 10: ...Table of Contents 10 ...
Страница 14: ...Introduction 14 ...
Страница 28: ...Quick start up guide 28 ...
Страница 30: ...Mechanical installation 30 ...
Страница 32: ...Electrical installation 32 ...
Страница 40: ...Drive configuration 40 ...
Страница 80: ...Communication 80 ...
Страница 82: ...Fault tracing 82 ...
Страница 85: ......