REM 543 Protection,
Monitoring and Control
Page 35
Technical Reference Manual
Part 1, General
ABB Network Partner
For detailed information about terminal connections for outputs, please refer to terminal
diagrams, where all the outputs are included with relay connector terminals.
For detailed technical data of the outputs, refer to the section “Technical Data”.
4.1.7.1.
High-speed double-pole power outputs (HSPO)
The high-speed power outputs PS1_4_HSPO1 ... PS1_4_HSPO5 can be connected as
double-pole outputs where the object to be controlled (e.g. a circuit breaker) is electri-
cally connected between the two relay contacts, see the figure below. The high-speed
double-pole power output is preferred to be used for tripping purposes.
Fig. 4.1.7.1.-1. High-speed double-pole power output (HSPO).
The high-speed power outputs PS1_4_HSPO1 ... PS1_4_HSPO5 can also be connected
as single-pole power outputs where the object to be controlled (e.g. a circuit breaker) is
electrically connected in series with the two relay contacts, see the figure below.
Fig. 4.1.7.1.-2. High-speed single-pole power output (HSPO).
+
-
cbcoil
CB
e.g.
PS1_4_HSPO1...
PS1_4_HSPO5
+
-
doubpole
CB
e.g.
PS1_4_HSPO1...
PS1_4_HSPO5