REM 543 Protection,
Monitoring and Control
Page 49
Technical Reference Manual
Part 1, General
ABB Network Partner
Table 2: Auxiliary power supplies
Table 3: Binary inputs
Table 4: Signal outputs
Table 5: Power outputs
Table 6: Environmental conditions
Type
PS1/240V
PS1/48V
Input voltage, ac
110/120/220/240 V
-
Input voltage, dc
110/125/220 V
24/48/60 V
Operating range
ac 85…110%, dc 80…120% of
rated value
dc 80…120% of rated value
Burden quiescent/operating
~20/~40 W
Ripple in dc auxiliary voltage
max. 12% of the dc value
Interruption time in auxiliary dc
voltage without resetting
<50 ms, 110 V and
<100 ms, 200 V
Internal overtemperature
indication
+78
°
C (+75…+83
°
C)
Operating range
18…265 V dc
(24/48/60/110/220 V dc)
Current drain
~2…25 mA
Power consumption/input
<0.8 W
Pulse counting (specific binary inputs), frequency
range
0…100 Hz
Rated voltage
250 V ac/dc
Continuous carry
5 A
Make and carry for 0.5 s
10 A
Make and carry for 3 s
8 A
Breaking capacity when control circuit time-constant
L/R <40 ms, at 48/110/220 V dc
1 A/0.25 A/0.15 A
Rated voltage
250 V ac/dc
Continuous carry
5 A
Make and carry for 0.5 s
30 A
Make and carry for 3 s
15 A
Breaking capacity when control circuit time-constant
L/R <40 ms, at 48/110/220 V dc
5 A/3 A/1 A
Minimum contact load
100 mA, 24 V ac/dc (2.4 VA)
HSPO (High-Speed Power Output)
5 ms faster than a power output (PO)
TCS (Trip Circuit
Supervision)
Control voltage range
20…265 V ac/dc
Current drain through the
supervision circuit
approx. 1.5 mA (0.99…1.72 mA)
Minimum voltage
(threshold) over a
contact
20 V ac/dc (15…20 V)
Specified service temperature range
-10…+55
°
C
Transport and storage temperature range
-40…+70
°
C
Enclosure class
Front side, flush-mounted
IP 54
Rear side, connection terminals
Note! A rear protective cover
(accessory) can be used to
protect and shield the rear of the
case
IP 20
Dry heat test
according to IEC 68-2-2
(BS 2011: Part 2.1 B)