SELGAPC2
IN_1
IN_2
OUT_1
OUT_2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_2
SELGAPC1_OUT_3
CB Closed Position
CB Open Posit ion
GUID-BC1E889E-D80E-4561-A70B-9986BFB374F7 V1 EN
Figure 31:
SELGAPC2
3.4.4.3
Binary outputs and LEDs
In the standard configuration A, the signals are routed to binary outputs and LEDs are
configured by OSWGAPCs. There are 16 OSWGAPC instances in total. They are
categorized in four groups, which include two master trip, four start, four trip and six
alarm signals. The
OSWGAPC
output is connected with binary outputs and LEDs via
SELGAPC3 and SELGAPC4.
•
SELGAPC3 is used to configure OSWGAPC signals to the protection relay's
binary outputs. SELGAPC4 is used to configure OSWGAPC signals to LEDs.
•
OSWGAPC1 and OSWGAPC2 are used for the master trip. The inputs are routed
from the protection function's operate and the circuit breaker failure's re-trip.
•
OSWGAPC3 to OSWGAPC6 are used for the start signal. The inputs are start
signals routed from the protection functions.
•
OSWGAPC7 to OSWGAPC10 are used for the trip signal. The inputs are
operation signals routed from the protection functions.
•
OSWGAPC11 to OSWGAPC16 are used for the alarm signal. The inputs are
alarm signals routed from the protection and monitoring functions.
1MRS758335 B
Section 3
REU611 standardized configuration
REU611
49
Application Manual