![ABB Relion Скачать руководство пользователя страница 46](http://html.mh-extra.com/html/abb/relion/relion_applications-manual_2787046.webp)
Channel number
Channel ID text
Level trigger mode
Binary channel 13
ROVPTOV3_START
1=positive or rising
Binary channel 14
FRPFRQ1_START
1=positive or rising
Binary channel 15
FRPFRQ2_START
1=positive or rising
Binary channel 16
PHPTOV_OPERATE
1=positive or rising
Binary channel 17
PHPTUV_OPERATE
1=positive or rising
Binary channel 18
ROVPTOV_OPERATE
1=positive or rising
Binary channel 19
PSPTUV/NSPTOV_OPERATE
1=positive or rising
Binary channel 20
FRPFRQ_OPERATE
1=positive or rising
Binary channel 21
SELGAPC1_Blocking 1
1=positive or rising
Binary channel 22
SELGAPC1_CB_Closed
1=positive or rising
Binary channel 23
SELGAPC1_CB_Open
1=positive or rising
Binary channel 24
SELGAPC1_External Trip
1=positive or rising
Binary channel 25
SG_1_ACT
1=positive or rising
Binary channel 26
SG_2_ACT
1=positive or rising
Binary channel 27
SG_3_ACT
1=positive or rising
Binary channel 28
SG_4_ACT
1=positive or rising
Binary channel 29
SG_5_ACT
1=positive or rising
Binary channel 30
SG_6_ACT
1=positive or rising
Binary channel 31
BUS_VT_MCB_OPEN
1=positive or rising
X120-BI3
OR
LED 7
TRIP CIRCUIT SUPERVISION
SELGAPC1
OUT_3
IN_3
TRPPTRC1_TRIP
TRPPTRC2_TRIP
TCSSCBR1
BLOCK
ALARM
TCSSCBR2
BLOCK
ALARM
SELGAPC4
OUT_7
IN_13
OSWGAPC12
OR
OUT
IN_2
IN_3
SELGAPC2
OUT_1
IN_2
OUT_2
CB Open Position
GUID-EC303A9E-DD21-4501-A0C9-82EBC49AA114 V1 EN
Figure 21:
Trip circuit supervision
Two separate trip circuit supervision functions are included, TCSSCBR1 for PO3
(X100:15-19) and TCSSCBR2 for PO4 (X100:20-24). Both functions are blocked by
the master trip (TRPPTRC1 and TRPPTRC2) and the circuit breaker open position.
The TCS alarm indication is connected to LED 7.
Section 3
1MRS758335 B
REU611 standardized configuration
40
REU611
Application Manual