X100 PO2
X100 SO1
COMMON ALARM INDICATION 1 & 2
OSWGAPC3
OR
OUT
OSWGAPC7
OR
OUT
SELGAPC3
OUT_2
IN_4
OUT_3
IN_8
TPGAPC1
IN1
OUT1
TPGAPC3
IN1
OUT1
PHPTOV1_START
PHPTOV2_START
PHPTOV3_START
PHPTUV1_START
PHPTUV3_START
ROVPTOV1_START
ROVPTOV2_START
ROVPTOV3_START
NSPTOV2_START
PSPTUV1_START
PSPTUV2_START
FRPFRQ1_START
FRPFRQ2_START
PHPTUV2_START
NSPTOV1_START
IN_1
IN_2
IN_3
IN_4
IN_5
IN_6
IN_7
IN_8
IN_9
IN_10
IN_11
IN_12
IN_13
IN_15
IN_14
PHPTOV1_OPERATE
PHPTOV2_OPERATE
PHPTOV3_OPERATE
IN_1
IN_2
IN_3
GUID-ABBA0E88-9D42-4D61-A3E9-DC321BA760B4 V2 EN
Figure 24:
Common alarm indication
The signal outputs from the protection relay are connected to give dedicated
information.
•
Start of any protection function PO2 (X100:8-9)
•
Operation (trip) of overvoltage protection function SO1 (X100:10-12)
TPGAPC functions are timers and they are used for setting the minimum pulse length
for the outputs. There are seven generic timers (TPGAPC1…7) available in the
protection relay.
3.4.4
Switch groups
In configuration A, the switch group function blocks are organized in four groups:
binary inputs, internal signal, GOOSE and binary outputs and LEDs.
1MRS758335 B
Section 3
REU611 standardized configuration
REU611
43
Application Manual