3.4.2
Functions
U
L1
U
L2
U
L3
U
L1
U
L2
U
L3
3U<
27
3U>
59
U2>
47O-
U1<
47U+
Uo>
59G
f>/f<,
df/dt
81
REMARKS
Optional
function
No. of
instances
Alternative
function to be
defined when
ordering
OR
3×
Io/Uo
Calculated
value
CONDITION MONITORING
AND SUPERVISION
CONTROL AND INDICATION
1)
MEASUREMENT
- U, Uo, f
- Limit value supervision
- Symmetrical components
VOLTAGE PROTECTION RELAY
STANDARD
CONFIGURATION
LOCAL HMI
A
COMMUNICATION
Protocols:
IEC 61850-8-1
Modbus®
Interfaces:
Ethernet: TX (RJ-45), FX (LC)
Serial:
RS-485
Redundant protocols:
HSR
PRP
RSTP
-
5
Analog interface types
1)
Current transformer
Voltage transformer
1)
Conventional transformer inputs
Object
Ctrl
2)
Ind
3)
CB
DC
ES
1
-
-
-
-
-
1)
Check availability of binary inputs/outputs
from technical documentation
2)
Control and indication function for
primary object
3)
Status indication function for
primary object
Master Trip
Lockout relay
94/86
PROTECTION
Uo
Uo
ALSO AVAILABLE
- Disturbance and fault recorders
- Event log and recorded data
- Local/Remote push button on LHMI
- Self-supervision
- Time synchronization: IEEE 1588 v2,
SNTP, IRIG-B
- User management
- Web-HMI
2×
2×
TCS
TCM
2×
3×
2×
3×
3×
2×
REU611
R
L
ESC
I
O
A
Control
Events
Measurements
Disturbance records
U
12
GUID-188F04CC-D6B0-4AB5-BDAB-BE4B993A605C V1 EN
Figure 14:
Functionality overview for configuration A
3.4.2.1
Default I/O connections
Table 11:
Default connections for binary inputs
Binary input
Description
Connector pins
X130-BI1
Blocking of overvoltage protection
X130:1-2
X130-BI2
Circuit breaker closed position indication
X130:3-4
X130-BI3
Circuit breaker open position indication
X130:5-6
X130-BI4
Bus voltage transformer MCB open
X130:7-8
Section 3
1MRS758335 B
REU611 standardized configuration
32
REU611