Blocking 2
ISWGAPC2
IN
OUT_1
OUT_2
OUT_3
OUT_4
OUT_5
OUT_6
OUT_7
OUT_8
OUT_9
OUT_10
OUT_11
OUT_12
OUT_13
OUT_14
OUT_15
PHPTOV1_BLOCK
PHPTOV2_BLOCK
PHPTOV3_BLOCK
PHPTUV1_BLOCK
PHPTUV2_BLOCK
PHPTUV3_BLOCK
ROVPTOV1_BLOCK
ROVPTOV2_BLOCK
ROVPTOV3_BLOCK
NSPTOV1_BLOCK
NSPTO V2_BLOCK
PSPTUV1_BLOCK
PSPTUV2_BLOCK
FRPFRQ1_BLOCK
FRPFRQ2_BLOCK
GUID-21043993-1044-4B8B-81E5-BF45A21D79CB V1 EN
Figure 29:
ISWGAPC2
3.4.4.2
Internal signal
The internal signal group is used to configure logic connections between function
blocks. There is one SELGAPC in the group. SELGAPC2 is used to configure TCS
blocking from the circuit breaker open or close position.
SELGAPC2
TCSSCBR1_BLOCK
TCSSCBR2_BLOCK
SELGAPC1_OUT_3
CB Closed Position
CB Open Posit ion
SELGAPC1_OUT_2
GUID-F60A5ABF-7569-44D7-B5E4-CC60F9F87D9E V1 EN
Figure 30:
Internal signal
SELGAPC2
SELGAPC2 inputs represent the circuit breaker closed and open positions from
SELGACP1. SELGAPC2 outputs are routed to the
BLOCK
input of the trip circuit
supervision TCSSCBR1 and TCSSCBR2.
By default, X100 PO3 and PO4 are both used for opening the circuit breaker.
TCSSCBR1 and TCSSCBR2 are both blocked by the circuit breaker open position. If
X100-PO3 is used for closing the circuit breaker, TCSSCBR1 needs to be blocked by
circuit breaker close position (
OUT_1
connection=
IN_1
). If X100-PO4 is used for
closing the circuit breaker, TCSSCBR2 needs to be blocked by the circuit breaker
close position (
OUT_2
connection=
IN_1
).
Section 3
1MRS758335 B
REU611 standardized configuration
48
REU611
Application Manual