3.4.3.2
Functional diagrams for disturbance recorder and trip circuit
supervision
RDRE1
C1
C2
C3
C4
C5
C6
C7
C8
C9
C10
C11
C12
C13
C14
C15
C16
C17
C18
C19
C20
C21
C22
C23
C24
C25
C26
C27
C28
C29
C30
C31
OR
OR
OR
OR
TRIGGERED
LED 6
DISTURBANCE RECORDER
PSPTUV1_OPERATE
PSPTUV2_OPERATE
NSPTOV1_OPERATE
NSPTO V2_OPERATE
PHPTUV2_OPERATE
PHPTUV1_OPERATE
PHPTUV3_OPERATE
ROVPTOV1_OPERATE
ROVPTOV2_OPERATE
ROVPTOV3_OPERATE
FRPFRQ1_OPERATE
FRPFRQ2_OPERATE
OSWGAPC11
OUT
IN_1
SELGAPC4
OUT_6
IN_12
PHPTO V3_START
PHPTOV2_START
PHPTOV1_START
PHPTUV1_START
PHPTUV3_START
PSPTUV2_START
SEL1_Blocking 1
SEL1_CB Closed
SEL1_CB_Open
PHPTUV2_START
SEL1_External_Trip
SG_1_ACT
SG_2_ACT
SG_3_ACT
SG_4_ACT
SG_5_ACT
SG_6_ACT
OR
PHPTO V2_OPERATE
PHPTOV1_OPERATE
PHPTO V3_OPERATE
PSPTUV1_START
NSPTOV1_START
NSPTOV2_START
ROVPTOV1_START
ROVPTOV2_START
ROVPTOV3_START
FRPFRQ1_START
FRPFRQ2_START
BUS_VT_MCB_OPEN
GUID-E2B78222-723F-42A9-9F6C-1AE1E3BCDF9F V1 EN
Figure 20:
Disturbance recorder
All start and operate signals from the protection stages are routed to trigger the
disturbance recorder or alternatively only to be recorded by the disturbance recorder
depending on the parameter settings. The active setting group is also to be recorded via
SG_1_ACT to SG_6_ACT. The disturbance recorder triggered signal indication is
connected to LED 6.
Table 15:
Disturbance recorder binary channel default value
Channel number
Channel ID text
Level trigger mode
Binary channel 1
PHPTOV1_START
1=positive or rising
Binary channel 2
PHPTOV2_START
1=positive or rising
Binary channel 3
PHPTOV3_START
1=positive or rising
Binary channel 4
PHPTUV1_START
1=positive or rising
Binary channel 5
PHPTUV2_START
1=positive or rising
Binary channel 6
PHPTUV3_START
1=positive or rising
Binary channel 7
PSPTUV1_START
1=positive or rising
Binary channel 8
PSPTUV2_START
1=positive or rising
Binary channel 9
NSPTOV1_START
1=positive or rising
Binary channel 10
NSPTOV2_START
1=positive or rising
Binary channel 11
ROVPTOV1_START
1=positive or rising
Binary channel 12
ROVPTOV2_START
1=positive or rising
Table continues on next page
1MRS758335 B
Section 3
REU611 standardized configuration
REU611
39
Application Manual