background image

Relion

®

 611 series

Voltage Protection and Control

REU611

Application Manual

Содержание Relion

Страница 1: ...Relion 611 series Voltage Protection and Control REU611 Application Manual ...

Страница 2: ......

Страница 3: ...Document ID 1MRS758335 Issued 2016 10 11 Revision B Product version 2 0 Copyright 2016 ABB All rights reserved ...

Страница 4: ... this document is furnished under a license and may be used copied or disclosed only in accordance with the terms of such license Trademarks ABB and Relion are registered trademarks of the ABB Group All other brand or product names mentioned in this document may be trademarks or registered trademarks of their respective holders Warranty Please inquire about the terms of warranty from your nearest ...

Страница 5: ...cted and communicate data and information via a network interface which should be connected to a secure network It is the sole responsibility of the person or entity responsible for network administration to ensure a secure connection to the network and to take the necessary measures such as but not limited to installation of firewalls application of authentication measures encryption of data inst...

Страница 6: ...nd concerning electrical equipment for use within specified voltage limits Low voltage directive 2006 95 EC This conformity is the result of tests conducted by ABB in accordance with the product standard EN 60255 26 for the EMC directive and with the product standards EN 60255 1 and EN 60255 27 for the low voltage directive The product is designed in accordance with the international standards of ...

Страница 7: ...ty package version 9 Operation functionality 10 Optional functions 10 Physical hardware 10 Local HMI 11 Display 12 LEDs 13 Keypad 13 Web HMI 14 Command buttons 15 Authorization 16 Audit trail 17 Communication 19 Self healing Ethernet ring 20 Ethernet redundancy 21 Secure communication 23 Section 3 REU611 standardized configuration 25 Standardized configuration 25 Switch groups 26 Input switch grou...

Страница 8: ...nctional diagrams for control 41 Switch groups 43 Binary inputs 44 Internal signal 48 Binary outputs and LEDs 49 GOOSE 67 Section 4 Protection relay s physical connections 69 Inputs 69 Energizing inputs 69 Phase voltage 69 Residual voltage 69 Auxiliary supply voltage input 69 Binary inputs 70 Outputs 70 Outputs for tripping and controlling 70 Outputs for signalling 71 IRF 71 Section 5 Glossary 73 ...

Страница 9: ... be used The manual can also be used when calculating settings 1 2 Intended audience This manual addresses the protection and control engineer responsible for planning pre engineering and engineering The protection and control engineer must be experienced in electrical power engineering and have knowledge of related technology such as protection schemes and principles 1MRS758335 B Section 1 Introd...

Страница 10: ...1850 engineering guide Point list manual Cyber security deployment guideline GUID 0777AFDA CADF 4AA9 946E F6A856BDF75E V1 EN Figure 1 The intended use of manuals in different lifecycles Product series and product specific manuals can be downloaded from the ABB Web site http www abb com relion 1 3 2 Document revision history Document revision date Product version History A 2016 02 22 2 0 First rele...

Страница 11: ...n icon indicates important information or warning related to the concept discussed in the text It might indicate the presence of a hazard which could result in corruption of software or damage to equipment or property The information icon alerts the reader of important facts and conditions The tip icon indicates advice on for example how to design your project or how to use a certain function Alth...

Страница 12: ... function starts the START output is set to TRUE This document assumes that the parameter setting visibility is Advanced 1 4 3 Functions codes and symbols Table 1 Functions included in the relay Function IEC 61850 IEC 60617 IEC ANSI Protection Residual overvoltage protection instance 1 ROVPTOV1 Uo 1 59G 1 Residual overvoltage protection instance 2 ROVPTOV2 Uo 2 59G 2 Residual overvoltage protectio...

Страница 13: ...GAPC SELGAPC SELGAPC Minimum pulse timer 2 pcs 4 TPGAPC TP TP Move 8 pcs instance 1 MVGAPC MV 1 MV 1 Control Circuit breaker control CBXCBR1 I O CB I O CB Condition monitoring and supervision Trip circuit supervision instance 1 TCSSCBR1 TCS 1 TCM 1 Trip circuit supervision instance 2 TCSSCBR2 TCS 2 TCM 2 Logging Disturbance recorder RDRE1 DR 1 DFR 1 Fault recorder FLTRFRC1 FR Measurement Three pha...

Страница 14: ...8 ...

Страница 15: ... by the IEC 61850 standard adds flexibility and value to end users as well as electrical system manufacturers The 611 series relays fully support the IEC 61850 standard for communication and interoperability of substation automation devices including fast GOOSE Generic Object Oriented Substation Event messaging and can now also benefit from the extended interoperability provided by Edition 2 of th...

Страница 16: ...http www abb com substationautomation or directly with the Update Manager in PCM600 2 2 Operation functionality 2 2 1 Optional functions IEEE 1588 time v2 synchronization High availability seamless redundancy protocol HSR Parallel redundancy protocol PRP 2 3 Physical hardware The protection relay consists of two main parts plug in unit and case The content depends on the ordered functionality Sect...

Страница 17: ...pe of communication modules Rated values of the current and voltage inputs are basic setting parameters of the protection relay The binary input thresholds are selectable within the range 16 176 V DC by adjusting the binary input setting parameters See the installation manual for more information about the case and the plug in unit The connection diagrams of different hardware modules are presente...

Страница 18: ...that supports two character sizes The character size depends on the selected language The amount of characters and rows fitting the view depends on the character size Table 4 Small display Character size1 Rows in the view Characters per row Small mono spaced 6 12 pixels 5 20 Large variable width 13 14 pixels 3 8 or more 1 Depending on the selected language The display view is divided into four bas...

Страница 19: ...n be configured with the LHMI WHMI or PCM600 2 4 3 Keypad The LHMI keypad contains push buttons which are used to navigate in different views or menus With the push buttons you can give open or close commands to one object in the primary circuit for example a circuit breaker a contactor or a disconnector The push buttons are also used to acknowledge alarms reset indications provide help and switch...

Страница 20: ...to take a secured HTTPS connection to WHMI using TLS encryption The WHMI is verified with Internet Explorer 8 0 9 0 10 0 and 11 0 WHMI is enabled by default WHMI offers several functions Programmable LEDs and event lists System supervision Parameter settings Measurement display Disturbance records Fault records Phasor diagram Signal configuration Importing Exporting parameters Report summary The m...

Страница 21: ...mand buttons Command buttons can be used to edit parameters and control information via the WHMI Table 5 Command buttons Name Description Enabling parameter editing Disabling parameter editing Writing parameters to the protection relay Refreshing parameter values Printing out parameters Committing changes to protection relay s non volatile flash memory Table continues on next page 1MRS758335 B Sec...

Страница 22: ...ecord files Viewing all fault records Clearing all fault records Importing settings Exporting settings Selecting all Clearing all selections Refreshing the parameter list view 2 6 Authorization Four user categories have been predefined for the LHMI and the WHMI each with different rights and default passwords The default passwords in the protection relay delivered from the factory can be changed w...

Страница 23: ...e reconstruction and examination of the sequence of system and security related events and changes in the protection relay Both audit trail events and process related events can be examined and analyzed in a consistent method with the help of Event List in LHMI and WHMI and Event Viewer in PCM600 The protection relay stores 2048 audit trail events to the nonvolatile audit trail Additionally 1024 p...

Страница 24: ... 61850 8 1 MMS WHMI FTP or LHMI Logout Successful logout from IEC 61850 8 1 MMS WHMI FTP or LHMI Password change Password changed Firmware reset Reset issued by user or tool Audit overflow Too many audit events in the time period Violation remote Unsuccessful login attempt from IEC 61850 8 1 MMS WHMI FTP or LHMI Violation local Unsuccessful login attempt from IEC 61850 8 1 MMS WHMI FTP or LHMI PCM...

Страница 25: ...IEC 61850 and Modbus Operational information and controls are available through these protocols However some communication functionality for example horizontal communication between the protection relays is only enabled by the IEC 61850 communication protocol The IEC 61850 communication implementation supports all monitoring and control functions Additionally parameter settings disturbance recordi...

Страница 26: ...tion of self healing loop topology it is essential that the external switches in the network support the RSTP protocol and that it is enabled in the switches Otherwise connecting the loop topology can cause problems to the network The protection relay itself does not support link down detection or RSTP The ring recovery process is based on the aging of the MAC addresses and the link up link down e...

Страница 27: ...bstation communication It is based on two complementary protocols defined in the IEC 62439 3 2012 standard parallel redundancy protocol PRP 1 and high availability seamless redundancy HSR protocol Both protocols rely on the duplication of all transmitted information via two Ethernet ports for one logical network connection Therefore both are able to overcome the failure of a link or switch with a ...

Страница 28: ...s SANs are either attached to one network only and can therefore communicate only with DANs and SANs attached to the same network or are attached through a redundancy box a device that behaves like a DAN Managed Ethernet switch IEC 61850 PRP Managed Ethernet switch GUID AA005F1B A30B 48F6 84F4 A108F58615A2 V1 EN Figure 7 PRP solution In case a laptop or a PC workstation is connected as a non PRP n...

Страница 29: ...h a redundancy box that acts as a ring element For example a 615 or 620 series protection relay with HSR support can be used as a redundancy box IEC 61850 HSR Ethernet switch Redundancy box Redundancy box Redundancy box X X Unicast traffic Message is recognized as a duplicate and is immediately forwarded X Sending device removes the message from the ring Devices not supporting HSR Sender Receiver ...

Страница 30: ...24 ...

Страница 31: ... A Table 10 Supported functions Function IEC 61850 A Protection Residual overvoltage protection ROVPTOV 3 Three phase undervoltage protection PHPTUV 3 Three phase overvoltage protection PHPTOV 3 Positive sequence undervoltage protection PSPTUV 2 Negative sequence overvoltage protection NSPTOV 2 Frequency protection FRPFRQ 2 Master trip TRPPTRC 2 Control Circuit breaker control CBXCBR 1 Condition m...

Страница 32: ...veral instances Connections of binary inputs to functions GOOSE signals to functions functions to functions functions to binary outputs and functions to LEDs have been preconnected through corresponding switch groups The real connection logic and the application configuration can be modified by changing the parameter values of the switch groups It is also possible to modify the real connection log...

Страница 33: ...gic is routed to switch group output GUID 1EFA82D5 F9E7 4322 87C2 CDADD29823BD V1 EN Figure 10 Output switch group OSWGAPC 3 2 3 Selector switch group SELGAPC The selector switch group SELGAPC has a number of inputs and outputs Every input and output has a read only description Each output can be set to be connected with one of the inputs via the OUT_x connection setting An output can also be set ...

Страница 34: ...GUID E3AEC7AB 2978 402D 8A80 C5DE9FED67DF V1 EN Figure 11 Selector switch group SELGAPC Section 3 1MRS758335 B REU611 standardized configuration 28 REU611 Application Manual ...

Страница 35: ...30 1 2 3 4 5 6 BI 4 BI 3 BI 2 BI 1 8 7 9 10 11 12 U12B 13 14 U1 15 16 U2 17 18 U3 Uo N N N N 60 N 210V 60 210V 60 210V 60 210V 60 210V GUID 45AA211F CF77 4974 BBF6 4FC34B46EF3B V1 EN Figure 12 Connection diagram for configuration A voltage protection with phase to phase voltage measurement 1MRS758335 B Section 3 REU611 standardized configuration REU611 29 Application Manual ...

Страница 36: ...16 U2 17 18 U3 Uo N N N N 60 N 210V 60 210V 60 210V 60 210V 60 210V GUID 90BD624C 28F1 4B93 8A2B 708E480A07A8 V1 EN Figure 13 Connection diagram for configuration A voltage protection with phase to earth voltage measurement Section 3 1MRS758335 B REU611 standardized configuration 30 REU611 Application Manual ...

Страница 37: ...es in the power system The protection relay with a standardized configuration is delivered from the factory with default settings and parameters The end user flexibility for incoming outgoing and internal signal designation within the protection relay enables this configuration to be further adapted to different primary circuit layouts and the related functionality needs by modifying the internal ...

Страница 38: ...tion function for primary object 3 Status indication function for primary object Master Trip Lockout relay 94 86 PROTECTION Uo Uo ALSO AVAILABLE Disturbance and fault recorders Event log and recorded data Local Remote push button on LHMI Self supervision Time synchronization IEEE 1588 v2 SNTP IRIG B User management Web HMI 2 2 TCS TCM 2 3 2 3 3 2 REU611 R L ESC I O A Control Events Measurements Di...

Страница 39: ...t supervision alarm 8 Bus VT MCB failure 3 4 2 2 Predefined disturbance recorder connections Table 14 Predefined analog channel setup Channel Description 1 Uo 2 U1 3 U2 4 U3 5 U1B Additionally all the digital inputs that are connected by default are also enabled with the setting Default triggering settings are selected depending on the connected input signal type Typically all protection START sig...

Страница 40: ...culated 3 4 3 1 Functional diagrams for protection The functional diagrams describe the protection functionality of the protection relay in detail and picture the factory default connections LED 1 SELGAPC4 OUT_1 IN_8 OSWGAPC7 OR OUT IN_1 IN_2 IN_3 OVERVOLTAGE PROTECTION INDICATION PHPTOV1 3U 1 59 1 BLOCK START OPERATE 3U PHPTOV2 3U 2 59 2 BLOCK START OPERATE 3U PHPTOV3 3U 3 59 3 BLOCK START OPERAT...

Страница 41: ...PHPTUV3 3U 3 27 3 BLOCK START OPERATE 3U GUID 0E0A1B18 45A8 4FDB BCFB 9FFC175CD53B V1 EN Figure 16 Undervoltage protection Three undervoltage protection stages PHPTUV1 3 offer protection against undervoltage conditions All operate signals are connected to the master trip and to alarm LED 2 1MRS758335 B Section 3 REU611 standardized configuration REU611 35 Application Manual ...

Страница 42: ...7 Residual overvoltage protection The residual overvoltage protection ROVPTOV provides earth fault protection by detecting abnormal level of residual voltage It can be used for example as a nonselective backup protection for the selective directional earth fault functionality All operate signals of these residual overvoltage protections are connected to the master trip and to alarm LED 3 Section 3...

Страница 43: ...RT OPERATE 3I GUID 1D8D400A 3ED1 4C24 BE3D A93EB046013D V1 EN Figure 18 Unbalance protection Four unbalance voltage protection functions are available two stages of positive sequence undervoltage protection PSPTUV and two stages of negative sequence overvoltage protection NSPTOV The operate signals of these unbalance voltage protections are connected to the master trip and to alarm LED 4 1MRS75833...

Страница 44: ... prevents damage to network components under unwanted frequency conditions The function also contains a selectable rate of change of the frequency gradient protection to detect an increase or decrease in the rapid changing power system frequency at an early stage This can be used as an early indication of a disturbance in the system The operate signals of these frequency protections are connected ...

Страница 45: ...e signals from the protection stages are routed to trigger the disturbance recorder or alternatively only to be recorded by the disturbance recorder depending on the parameter settings The active setting group is also to be recorded via SG_1_ACT to SG_6_ACT The disturbance recorder triggered signal indication is connected to LED 6 Table 15 Disturbance recorder binary channel default value Channel ...

Страница 46: ...ising Binary channel 26 SG_2_ACT 1 positive or rising Binary channel 27 SG_3_ACT 1 positive or rising Binary channel 28 SG_4_ACT 1 positive or rising Binary channel 29 SG_5_ACT 1 positive or rising Binary channel 30 SG_6_ACT 1 positive or rising Binary channel 31 BUS_VT_MCB_OPEN 1 positive or rising X120 BI3 OR LED 7 TRIP CIRCUIT SUPERVISION SELGAPC1 OUT_3 IN_3 TRPPTRC1_TRIP TRPPTRC2_TRIP TCSSCBR1...

Страница 47: ...SWGAPC2 OR IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 IN_9 IN_10 IN_11 OUT IN_12 IN_13 IN_15 IN_14 PHPTOV1_OPERATE PHPTOV2_OPERATE PHPTOV3_OPERATE PHPTUV1_OPERATE PHPTUV3_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERTAE NSPTOV2_OPERATE PSPTUV1_OPERATE PSPTUV2_OPERATE FRPFRQ1_OPERTAE FRPFRQ2_OPERTAE PHPTUV2_OPETATE NSPTOV1_OPERATE GUID FBD41DB4 5D20 46F7 9D09 04318A7EE553 V2 EN Figure 22 Mas...

Страница 48: ... CB Closed Position CB Open Position CBXCBR1 ENA_OPEN SELECTED EXE_OP EXE_CL ENA_CLOSE BLK_OPEN BLK_CLOSE AU_OPEN AU_CLOSE POSOPEN POSCLOSE OPENPOS CLOSEPOS OKPOS OPEN_ENAD CLOSE_ENAD TRIP SYNC_ITL_BYP OP_REQ CL_REQ SYNC_OK GUID 798F8D1E A9AA 47A1 8A27 EAB36E989637 V2 EN Figure 23 Circuit breaker control The ENA_CLOSE input which enables the closing of the circuit breaker is interlocked by two mas...

Страница 49: ...ID ABBA0E88 9D42 4D61 A3E9 DC321BA760B4 V2 EN Figure 24 Common alarm indication The signal outputs from the protection relay are connected to give dedicated information Start of any protection function PO2 X100 8 9 Operation trip of overvoltage protection function SO1 X100 10 12 TPGAPC functions are timers and they are used for setting the minimum pulse length for the outputs There are seven gener...

Страница 50: ...FRQ1 FRPFRQ2 CBXCBR1 TCSSCBR2 TCSSCBR1 Internal Signal SELGAPC1 Binary Inputs ISWGAPC2 ISWGAPC1 SELGAPC2 Blocking TCS Blocking ISWGAPC9 GOOSE Blocking ISWGAPC10 GOOSE Block CB Alarm Trip Start Master trip GUID DD46D20E 10C3 4190 988E DB2C8E1E906E V1 EN Figure 25 Configuration A switch group overview 3 4 4 1 Binary inputs The binary inputs group includes one SELGAPC and two ISWGAPCs SELGAPC1 is use...

Страница 51: ...PTOV1_BLOCK ROVPTOV2_BLOCK ROVPTOV3_BLOCK NSPTOV1_BLOCK NSPTOV2_BLOCK PSPTUV1_BLOCK PSPTUV2_BLOCK FRPFRQ1_BLOCK FRPFRQ2_BLOCK X130 BI4 GUID 061E1E21 E166 4597 99F7 4770E336775A V1 EN Figure 26 Binary inputs SELGAPC1 SELGAPC1 has inputs from protection relay binary inputs IN_1 IN_4 are binary inputs from X130 An always true signal is connected to IN_5 SELGAPC1 outputs are used to route inputs to di...

Страница 52: ...e OUT_1 OUT_2 OUT_3 OUT_4 OUT_5 OUT_6 OUT_7 OUT_8 OUT_9 OUT_10 OUT_11 TRPTTRC1_RST_LKOUT TRPTTRC2_RST_LKOUT PROTECTION_BI_SG_4 Setting Group 4 Blocking 2 ISWGAPC2_IN BUS_VT_MCB_ OPEN BUS_VT_MCB_OPEN_ALARM GUID 80A08942 C2E5 48CB 94C3 2A803058F830 V2 EN Figure 27 SELGAPC1 ISWGAPC1 ISWGAPC1 is used to select the protection functions to be blocked by changing the ISWGAPC1 parameters ISWGAPC1 input is...

Страница 53: ...OV2_BLOCK PSPTUV1_BLOCK PSPTUV2_BLOCK FRPFRQ1_BLOCK FRPFRQ2_BLOCK GUID 65F2F3B6 3D6D 4126 891E 9C7AD6122367 V1 EN Figure 28 ISWGAPC1 ISWGAPC2 ISWGAPC2 is used to select the protection functions to be blocked by changing ISWGAPC2 parameters ISWGAPC2 input is routed from SELGAPC1 output OUT_13 Blocking 2 ISWGAPC2 outputs are connected to the BLOCK inputs of the protection functions 1MRS758335 B Sect...

Страница 54: ...CSSCBR2_BLOCK SELGAPC1_OUT_3 CB Closed Position CB Open Position SELGAPC1_OUT_2 GUID F60A5ABF 7569 44D7 B5E4 CC60F9F87D9E V1 EN Figure 30 Internal signal SELGAPC2 SELGAPC2 inputs represent the circuit breaker closed and open positions from SELGACP1 SELGAPC2 outputs are routed to the BLOCK input of the trip circuit supervision TCSSCBR1 and TCSSCBR2 By default X100 PO3 and PO4 are both used for open...

Страница 55: ... SELGAPC4 SELGAPC3 is used to configure OSWGAPC signals to the protection relay s binary outputs SELGAPC4 is used to configure OSWGAPC signals to LEDs OSWGAPC1 and OSWGAPC2 are used for the master trip The inputs are routed from the protection function s operate and the circuit breaker failure s re trip OSWGAPC3 to OSWGAPC6 are used for the start signal The inputs are start signals routed from the...

Страница 56: ...RT PHPTUV1_START PHPTUV2_START PHPTUV3_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START FRPFRQ1_START FRPFRQ2_START NSPTOV1_START NSPTOV2_START PSPTUV1_START PSPTUV2_START PHPTOV1_OPERATE PHPTOV2_OPERATE PHPTOV3_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE FRPFRQ1_OPERATE FRPFRQ2_OPERATE PSPTUV1_OPERATE PSPTUV2_OPERATE NSPTOV1_OPERATE...

Страница 57: ...2_START PHPTOV1_OPERATE PHPTOV2_OPERATE PHPTOV3_OPERATE PHPTUV1_OPERATE PHPTUV2_OPERATE PHPTUV3_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE FRPFRQ1_OPERATE FRPFRQ2_OPERATE NSPTOV1_OPERATE NSPTOV2_OPERATE PSPTUV1_OPERATE PSPTUV2_OPERATE OSWGAPC8 OSWGAPC7 OSWGAPC10 OSWGAPC9 Start 1 Start 2 OSWGAPC4 OSWGAPC5 Start 3 Start 4 OSWGAPC6 LED1 LED2 LED3 LED4 LED5 LED6 LED7 LED8 OSWGAPC12 Ala...

Страница 58: ...UT1 IN2 OUT2 TPGAPC7 IN1 OUT1 IN2 OUT2 TPGAPC6 IN1 OUT1 IN2 OUT2 TPGAPC5 IN1 OUT1 IN2 OUT2 TPGAPC4 IN1 OUT1 IN2 OUT2 TPGAPC3 IN1 OUT1 IN2 OUT2 TPGAPC2 IN1 OUT1 IN2 OUT2 GUID EE736EA4 3EF1 4581 BB5A FE060E1483B9 V1 EN Figure 34 SELGAPC3 SELGAPC4 SELGAPC4 is used to configure the OSWGAPC outputs to LEDs Master trip signals are connected to SELGAPC4 via TRPPTRC Start trip and alarm signals are connec...

Страница 59: ...m 4 Alarm 5 Alarm 6 CB Close CB Open 1 CB Open 2 CBXCBR_EXE_OP TRPPTRC1_TRIP GUID 80F9A51C 77DC 4BCF BE66 EAAD07B014BB V1 EN Figure 35 SELGAPC4 Master trip OSWGAPCs OSWGAPC1 and OSWGAPC2 are used to route the protection function operate signals to master trip OSWGAPC1 and OSWGAPC2 have the same inputs from the protection function s operate signals The output is connected to TRPPTRC function 1MRS75...

Страница 60: ...E FRPFRQ2_OPERATE NSPTOV1_OPERATE PHPTOV1_OPERATE NSPTOV2_OPERATE PHPTUV1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE PHPTOV3_OPERATE PHPTOV2_OPERATE IN_14 IN_15 PSPTUV1_OPERATE PSPTUV2_OPERATE GUID 3808B480 39FF 4E00 8340 BBD1497AF4E2 V1 EN Figure 36 OSWGAPC1 Section 3 1MRS758335 B REU611 standardized configuration 54 REU611 Application Manual ...

Страница 61: ...ERATE PHPTOV3_OPERATE PHPTOV2_OPERATE IN_14 IN_15 PSPTUV1_OPERATE PSPTUV2_OPERATE GUID 9D1302AD C7CF 4081 83E4 CC1BB38775AE V1 EN Figure 37 OSWGAPC2 Start OSWGAPCs OSWGAPC instances 3 6 are used to configure the protection start signals These four OSWGAPCs have the same inputs from the protection function start signals The output is routed to SELGAPC3 via TPGAPC timer and routed to SELGAPC4 direct...

Страница 62: ...PFRQ1_START FRPFRQ2_START NSPTOV1_START PHPTOV1_START NSPTOV2_START PHPTUV1_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START PHPTOV3_START PHPTOV2_START IN_14 IN_15 PSPTUV1_START PSPTUV2_START GUID 1CEEF190 B5CB 40C0 8D3B B85233DB3BDF V1 EN Figure 38 OSWGAPC3 Section 3 1MRS758335 B REU611 standardized configuration 56 REU611 Application Manual ...

Страница 63: ...PFRQ1_START FRPFRQ2_START NSPTOV1_START PHPTOV1_START NSPTOV2_START PHPTUV1_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START PHPTOV3_START PHPTOV2_START IN_14 IN_15 PSPTUV1_START PSPTUV2_START GUID BBEFEA55 AEDB 44D2 943B C0151C9C7D3C V1 EN Figure 39 OSWGAPC4 1MRS758335 B Section 3 REU611 standardized configuration REU611 57 Application Manual ...

Страница 64: ...PFRQ1_START FRPFRQ2_START NSPTOV1_START PHPTOV1_START NSPTOV2_START PHPTUV1_START ROVPTOV1_START ROVPTOV2_START ROVPTOV3_START PHPTOV3_START PHPTOV2_START IN_14 IN_15 PSPTUV1_START PSPTUV2_START GUID 37731A72 0467 4010 8A5F 29834699000A V1 EN Figure 40 OSWGAPC5 Section 3 1MRS758335 B REU611 standardized configuration 58 REU611 Application Manual ...

Страница 65: ..._START PHPTOV2_START PSPTUV1_START PSPTUV2_START GUID 21366E41 D912 47F4 8E79 0A1897838DE8 V1 EN Figure 41 OSWGAPC6 Trip OSWGAPCs OSWGAPC instances 7 10 are used to configure the protection operate signals which belong to the trip group These four OSWGAPCs have same inputs from the operate signals of the protection functions The output is routed to SELGAPC3 via TPGAPC timer and routed to SELGAPC4 ...

Страница 66: ...TE FRPFRQ2_OPERATE PSPTUV1_OPERATE PHPTOV1_OPERATE PSPTUV2_OPERATE PHPTUV1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE PHPTOV3_OPERATE PHPTOV2_OPERATE IN_14 IN_15 NSPTOV1_OPERATE NSPTOV2_OPERATE GUID 4C59046E A106 47B2 9278 872145522C9A V1 EN Figure 42 OSWGAPC7 Section 3 1MRS758335 B REU611 standardized configuration 60 REU611 Application Manual ...

Страница 67: ...TE FRPFRQ2_OPERATE PSPTUV1_OPERATE PHPTOV1_OPERATE PSPTUV2_OPERATE PHPTUV1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE PHPTOV3_OPERATE PHPTOV2_OPERATE IN_14 IN_15 NSPTOV1_OPERATE NSPTOV2_OPERATE GUID 89D0D99C 9A90 4F63 9E25 251108BFA4B3 V1 EN Figure 43 OSWGAPC8 1MRS758335 B Section 3 REU611 standardized configuration REU611 61 Application Manual ...

Страница 68: ...TE FRPFRQ2_OPERATE PSPTUV1_OPERATE PHPTOV1_OPERATE PSPTUV2_OPERATE PHPTUV1_OPERATE ROVPTOV1_OPERATE ROVPTOV2_OPERATE ROVPTOV3_OPERATE PHPTOV3_OPERATE PHPTOV2_OPERATE IN_14 IN_15 NSPTOV1_OPERATE NSPTOV2_OPERATE GUID 689B84B6 25A0 4CB7 A374 ED2E73A41A91 V1 EN Figure 44 OSWGAPC9 Section 3 1MRS758335 B REU611 standardized configuration 62 REU611 Application Manual ...

Страница 69: ...OPERATE PHPTOV3_OPERATE PHPTOV2_OPERATE IN_14 IN_15 NSPTOV1_OPERATE NSPTOV2_OPERATE GUID BA32398F 8C21 4566 9C0F A7874307413C V1 EN Figure 45 OSWGAPC10 Alarm OSWGAPCs OSWGAPC instances 11 16 are used to configure the alarm signals which belong to the alarm group These six OSWGAPCs have same inputs from the alarm signals The output is routed to SELGAPC3 via TPGAPC timer and routed to SELGAPC4 direc...

Страница 70: ...638 3D65 4A83 BD3A CCCF5C4F9CFC V1 EN Figure 46 OSWGAPC11 Alarm 2 TPGAPC5_IN2 SELGAPC4_IN_13 OSWGAPC12 OUT IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 IN_9 IN_10 IN_11 IN_12 TRPPTRC1_CL_LKOUT TRPPTRC2_CL_LKOUT RDRE_TRIGGERED SELGAPC1_OUT_6 TCSSCBR2_ALARM TCSSCBR1_ALARM BUS_VT_MCB_OPEN OVERVOLTAGE_OPERATE UNDERVOLTAGE_OPERATE External Trip GUID D3C08406 962B 44DB B830 B53093100311 V1 EN Figure 47 OSWGA...

Страница 71: ...54F 3B7B 4CE0 8295 B7F038A2D45B V1 EN Figure 48 OSWGAPC13 Alarm 4 TPGAPC6_IN2 SELGAPC4_IN_15 OSWGAPC14 OUT IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 IN_9 IN_10 IN_11 IN_12 TRPPTRC1_CL_LKOUT TRPPTRC2_CL_LKOUT RDRE_TRIGGERED SELGAPC1_OUT_6 TCSSCBR2_ALARM TCSSCBR1_ALARM BUS_VT_MCB_OPEN OVERVOLTAGE_OPERATE UNDERVOLTAGE_OPERATE External Trip GUID 57BA3BF3 AEFD 4BEF 9B1E DEE4C88F635B V1 EN Figure 49 OSWGA...

Страница 72: ...B97 C5D5 419E 8A17 E70CF2D1AB2D V1 EN Figure 50 OSWGAPC15 Alarm 6 TPGAPC7_IN2 SELGAPC4_IN_17 OSWGAPC16 OUT IN_1 IN_2 IN_3 IN_4 IN_5 IN_6 IN_7 IN_8 IN_9 IN_10 IN_11 IN_12 TRPPTRC1_CL_LKOUT TRPPTRC2_CL_LKOUT RDRE_TRIGGERED SELGAPC1_OUT_6 TCSSCBR2_ALARM TCSSCBR1_ALARM BUS_VT_MCB_OPEN OVERVOLTAGE_OPERATE UNDERVOLTAGE_OPERATE External Trip GUID 34F936D2 922C 4805 8350 25028A79223D V1 EN Figure 51 OSWGA...

Страница 73: ...onnected to ISWGAPC10 ISWGAPC10 is used to configure the GOOSE input signal to block the circuit breaker open or close operation CBXCBR1_BLK_CLOSE CBXCBR1_BLK_OPEN GOOSERCV_BIN 1 GOOSERCV_BIN 0 OR ISWGAPC9 GOOSE Blcoking GOOSERCV_BIN 3 GOOSERCV_BIN 2 OR GOOSE External Trip GOOSERCV_BIN 5 GOOSERCV_BIN 4 GOOSERCV_BIN 19 OR ISWGAPC10 GOOSE Block CB PHPTOV1_BLOCK PHPTOV2_BLOCK PHPTOV3_BLOCK PHPTUV1_BL...

Страница 74: ...SPTOV2_BLOCK PSPTUV1_BLOCK PSPTUV2_BLOCK GUID 0FCCA7F3 9413 49E1 8DF9 A46703C2DBAF V1 EN Figure 53 ISWGAPC9 ISWGAPC10 ISWGAPC10 is used to block the circuit breaker operation from the received GOOSE signals ISWGAPC10 inputs are received GOOSE signals from GOOSERCV_BIN 4 to GOOSERCV_BIN 19 The outputs are connected to block the circuit breaker s close and open operation ISWGAPC10 IN OUT_1 OUT_2 CBX...

Страница 75: ...esidual voltage Terminal Description X130 17 18 Uo 4 1 2 Auxiliary supply voltage input The auxiliary voltage of the protection relay is connected to terminals X100 1 2 At DC supply the positive lead is connected to terminal X100 1 The permitted auxiliary voltage range AC DC or DC is marked on the top of the LHMI of the protection relay Table 19 Auxiliary voltage supply Terminal Description X100 1...

Страница 76: ...puts for tripping and controlling Output contacts PO1 PO2 PO3 and PO4 are heavy duty trip contacts capable of controlling most circuit breakers On delivery from the factory the trip signals from all the protection stages are routed to PO3 and PO4 Table 21 Output contacts Terminal Description X100 6 PO1 NO X100 7 PO1 NO X100 8 PO2 NO X100 9 PO2 NO X100 15 PO3 NO TCS resistor X100 16 PO3 NO X100 17 ...

Страница 77: ... 2 3 IRF The IRF contact functions as an output contact for the self supervision system of the protection relay Under normal operating conditions the protection relay is energized and the contact is closed X100 3 5 When a fault is detected by the self supervision system or the auxiliary voltage is disconnected the output contact drops off and the contact closes X100 3 4 Table 23 IRF contact Termin...

Страница 78: ...72 ...

Страница 79: ... availability seamless redundancy HTTPS Hypertext Transfer Protocol Secure IEC International Electrotechnical Commission IEC 61850 International standard for substation communication and modeling IEC 61850 8 1 A communication protocol based on the IEC 61850 standard series IED Intelligent electronic device protection and control relay IEEE 1588 v2 Standard for a Precision Clock Synchronization Pro...

Страница 80: ...al communication protocol developed by the Modicon company in 1979 Originally used for communication in PLCs and RTU devices PCM600 Protection and Control IED Manager PO Power output PRP Parallel redundancy protocol REU611 Voltage protection and control relay RJ 45 Galvanic connector type RS 485 Serial link according to EIA standard RS485 RSTP Rapid spanning tree protocol SAN Single attached node ...

Страница 81: ...75 ...

Страница 82: ......

Страница 83: ......

Страница 84: ... Voltage Products Distribution Automation P O Box 699 FI 65101 VAASA Finland Phone 358 10 22 11 Fax 358 10 22 41599 www abb com mediumvoltage www abb com substationautomation 1MRS758335 B Copyright 2016 ABB All rights reserved ...

Отзывы: