Section 7
Checking installation
7.1
Identifying hardware and software version
GUID-7527A986-F827-4104-B0E9-C62B1B0EF706 v1
The information of hardware and software versions of the IED are available on the label attached on
the case of the IED. There are also module labels that can be used to identify the different modules
inside the IED (such as input-output cards and so on).
7.2
Checking mounting
GUID-50578D7B-23D4-45B0-BB10-D3108EEF9B97 v2
Check that all fixing screws are tight and that all cables are connected.
7.3
Checking the power supply
M11725-2 v6
Do not insert anything else to the female connector but the corresponding male
connector. Inserting anything else (such as a measurement probe) may damage the
female connector and prevent a proper electrical contact between the printed circuit
board and the external wiring connected to the screw terminal block.
Check that the auxiliary supply voltage remains within the permissible input voltage range under all
operating conditions. Check that the polarity is correct before energizing the IED.
7.4
Energizing the IED
GUID-E40DE80C-8DA4-4E17-876C-4CC3CE706347 v5
Before connecting the auxiliary power, check that the terminal strip is wired and placed correctly.
Remove the protective film from the top side of the unit.
During IED start-up, you can observe the internal fail relay that should change state to ready after
around 1 minute.
In order to get the following information in SAM600-IO, the service kit is need. For
more information on service kit, refer
SAM600-IO Technical manual
.
During IED start-up, you can observe the following sequence:
1.
The Green Ready LED starts to flash.
2.
The LCD lights up and starting... is displayed.
3.
The main menu is displayed. A final steady green Ready LED indicates a successful start-up of
the device.
If the self supervision of the IED detects a diagnostic error during the start-up process, the green
Ready LED flashes. Further information on the error may be visible on the local HMI under
Main
menu/Diagnostics /IED status/General
. Note down the displayed information as reference when
contacting Hitachi Power Grids technical support.
1MRK 514 030-UEN Rev. C
Section 7
Checking installation
Switchgear control unit SAM600-IO
31
Installation manual