A071222 V2 EN
Figure 61:
Warning
Table 17:
Warning indications and codes
Warning indication
Warning code
Additional information
Warning
Watchdog reset
10
A watchdog reset has occurred.
Warning
Power down det.
11
The auxiliary supply voltage has dropped
too low.
Warning
IEC61850 error
20
Error when building the IEC 61850 data
model.
Warning
Modbus error
21
Error in the Modbus communication.
Warning
DNP3 error
22
Error in the DNP3 communication.
Warning
Dataset error
24
Error in the Data set(s).
Warning
Report cont. error
25
Error in the Report control block(s).
Warning
GOOSE contr. error
26
Error in the GOOSE control block(s).
Warning
SCL config error
27
Error in the SCL configuration file or the file
is missing.
Warning
Logic error
28
Too many connections in the
configuration.
Warning
SMT logic error
29
Error in the SMT connections.
Warning
GOOSE input error
30
Error in the GOOSE connections.
Warning
GOOSE rec. error
32
Error in the GOOSE message receiving.
Warning
AFL error
33
Analog channel configuration error.
Warning
Unack card comp.
40
A new composition has not been
acknowledged/accepted.
Table continues on next page
1MRS756708 A
Section 7
Troubleshooting
615 series
85