171
Description
Parameter
(channel 0)
Setting range Default setting Customer
’
s
setting
Connection type
V204
0 = loop
1 = star
0
Line-idle state
V205
0 = light off
1 = light on
0
Optional communication
module
V206
0 = not in use
1 = in use
0
Table 8.-4
Parameters for the disturbance recorder
Description
Parameter
(channel 0)
Setting range Default setting Customer
’
s
setting
Sampling rate
M15
800/960 Hz
400/480 Hz
50/60 Hz
800 Hz
Station identification/unit
number
M18
0...9999
0
Name of the feeder
M20
Max 16
characters
- ABB -
Analog channel
conversion factor and unit
for I
a
, I
b
and I
c
M80, M81, M82 Factor
0...65535, unit
(A, kA), e.g. 10,
kA
00001, CT
Analog channel
conversion factor and unit
for the ground-fault
current
M83
Factor
0...65535, unit
(A, kA), e.g. 10,
kA
00001, CT
Internal trigger signals'
checksum
V236
0...16383
682
Internal trigger signal's
edge
V237
0...16383
0
Checksum of internal
signal storing mask
V238
0...16383
751
Post-triggering recording
length
V240
0...100%
50 %
External trigger signal's
checksum
V241
0...31
0
External trigger signal's
edge
V242
0...31
0
Checksum of external
signal storing mask
V243
0...31
0
Table 8.-5
Auto-reclose parameters
Description
Parameter
(channel 0)
Value
Default setting Customer
’
s
setting
CB Closing time
V121
0.1...10 s
0.2 s
Pickup delay of element
51P
V122
0...300 s
300 s
Pickup delay of element
51N
V123
0...300 s
300 s
Reclaim time
V124
3...300 s
10 s
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610
1MRS755535
Содержание RELION REF610
Страница 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 20: ...20 ...
Страница 164: ...164 ...
Страница 175: ......