129
Parameters
O41
...
O49
and
O51
control the physical output contacts
which can be connected to circuit breakers, for instance.
Parameters for IEC 60870-5-103 remote communication protocol
Table 5.1.17.-12
Settings
Description
Parameter
(channel 507)
R, W, P
Value
Unit address of the relay
507V200
R, W
1...254
Data transfer rate (IEC 60870-5-
103), kbps
507V201
R, W (P)
9.6/4.8
Parameters for Modbus remote communication protocol
Table 5.1.17.-13
Settings
Description
Parameter
(channel 504)
R, W, P
Value
User-defined register 1
504V1
R, W
0...65535
a)
User-defined register 2
504V2
R, W
0...65535
a)
User-defined register 3
504V3
R, W
0...65535
a)
User-defined register 4
504V4
R, W
0...65535
a)
User-defined register 5
504V5
R, W
0...65535
a)
User-defined register 6
504V6
R, W
0...65535
a)
User-defined register 7
504V7
R, W
0...65535
a)
User-defined register 8
504V8
R, W
0...65535
a)
User-defined register 9
504V9
R, W
0...65535
a)
User-defined register 10
504V10
R, W
0...65535
a)
User-defined register 11
504V11
R, W
0...65535
a)
User-defined register 12
504V12
R, W
0...65535
a)
User-defined register 13
504V13
R, W
0...65535
a)
User-defined register 14
504V14
R, W
0...65535
a)
User-defined register 15
504V15
R, W
0...65535
a)
User-defined register 16
504V16
R, W
0...65535
a)
Unit address of the relay
504V200
R, W
1...254
Data transfer rate (Modbus),
kbps
504V201
R, W
9.6/4.8/2.4/1.2/0.3
Modbus link parity
504V220
R, W
0 = even
1 = odd
2 = no parity
CRC order of Modbus RTU link
504V221
R, W
0 = low/high
1 = high/low
a)
The default value is 0.
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610
1MRS755535
Содержание RELION REF610
Страница 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 20: ...20 ...
Страница 164: ...164 ...
Страница 175: ......