Table 5.1.15.1.-7
Mapping of Modbus data: analog data
Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
Phase current I
a
x I
n
(CT)
404
0...5000
0...50 x FLA
Phase current I
b
x I
n
(CT)
405
0...5000
0...50 x FLA
Phase current I
c
x I
n
(CT)
406
0...5000
0...50 x FLA
Ground-fault current x I
n
(CT)
407
0...20000
0...2000% I
n
(CT)
Phase unbalance
408
0...100
0...100%
Table 5.1.15.1.-8
Mapping of Modbus data: digital data
Description
HR/IR address (.bit)
DI/Coil bit
address
Writeable
Value
range
Comment
Pickup signal from element 51P
409.00
1
0/1
1 = activated
Pickup signal from element 51P CD
409.01
2
Trip signal from element 51P
409.02
3
0/1
1 = activated
Trip signal from element 51P CD
409.03
4
Pickup signal from element 50P-1
409.04
5
0/1
1 = activated
Pickup signal from element 50P-1 CD
409.05
6
Trip signal from element 50P-1
409.06
7
0/1
1 = activated
Trip signal from element 50P-1 CD
409.07
8
Pickup signal from element 50P-2
409.08
9
0/1
1 = activated
Pickup signal from element 50P-2 CD
409.09
10
Trip signal from element 50P-2
409.10
11
0/1
1 = activated
Trip signal from element 50P-2 CD
409.11
12
Pickup signal from element 51N
409.12
13
0/1
1 = activated
Pickup signal from element 51N CD
409.13
14
Trip signal from element 51N
409.14
15
0/1
1 = activated
Trip signal from element 51N CD
409.15
16
Pickup signal from element 50N
410.00
17
0/1
1 = activated
Pickup signal from element 50N CD
410.01
18
Trip signal from element 50N
410.02
19
0/1
1 = activated
Trip signal from element 50N CD
410.03
20
Pickup signal from element 46
410.04
21
0/1
1 = activated
Pickup signal from element 46 CD
410.05
22
Trip signal from element 46
410.06
23
0/1
1 = activated
Trip signal from element 46 CD
410.07
24
Pickup signal from element 49
410.08
25
0/1
1 = activated
Pickup signal from element 49 CD
410.09
26
Alarm signal from element 49
410.10
27
0/1
1 = activated
Alarm signal from element 49 CD
410.11
28
Trip signal from element 49
410.12
29
0/1
1 = activated
Trip signal from element 49 CD
410.13
30
Trip signal from element ARC (light and
current)
410.14
31
0/1
1 = activated
96
REF610
REF610
Feeder Protection Relay
Technical Reference Manual - ANSI Version