127
Description
Channel
Parameter (R)
Value
CB position
0,3
I7
0 = undefined
1 = closed
2 = open
3 = undefined
DI1 status
0,2
I8
0/1
a)
DI2 status
0,2
I9
0/1
a)
DI3 status
0,2
I10
0/1
a)
DI4 status
0,2
I11
0/1
a)
DI5 status
0,2
I12
0/1
a)
a)
When the value is 1, the digital input is energized.
Each protection element has its internal output signal. These signals can be read
with parameters
O1
...
O26
and the recorded functions with parameters
O61
...
O86
.
The state of the output contacts can be read or changed with parameters
O41
...
O49
and the recorded functions read with parameters
O101
...
O109
.
Table 5.1.17.-10
Output signals
Status of the
protection
elements
Channel
State of element
(R)
Recorded
functions (R)
Value
Pickup of
element 51P
0,1
O1
O61
0/1
Trip of element
0,1
O2
O62
0/1
Pickup of
element 50P-1
0,1
O3
O63
0/1
Trip of element
element 50P-1
0,1
O4
O64
0/1
Pickup of
element 50P-2
0,1
O5
O65
0/1
Trip of element
50P-2
0,1
O6
O66
0/1 ;
Pickup of
element 51N
0,1
O7
O67
0/1
Trip of element
51N
0,1
O8
O68
0/1
Pickup of
element 50N
0,1
O9
O69
0/1
Trip of element
50N
0,1
O10
O70
0/1
Pickup of
element 46
0,1
O11
O71
0/1
Trip of element
46
0,1
O12
O72
0/1
Pickup of
element 49
0,1
O13
O73
0/1
Alarm of element
49
0,1
O14
O74
0/1
Trip of element
49
0,1
O15
O75
0/1
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610
1MRS755535
Содержание RELION REF610
Страница 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 20: ...20 ...
Страница 164: ...164 ...
Страница 175: ......