153
Table 5.2.4.-6
Non-trip output SO1 and optional SO4 and SO5
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
(5 A/3 A/1 A for series connection
of SO4 and SO5)
Minimum contact load
100 mA at 24 V AC/DC
Table 5.2.4.-7
Non-trip output SO2, optional SO3, and IRF output
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
10 A
Make and carry for 0.5 s
15 A
Breaking capacity when the control-circuit time constant
L/R <40 ms, at 48/110/220 V DC
1 A/0.25 A/0.15 A
Minimum contact load
100 mA at 24 V AC/DC
Table 5.2.4.-8
Trip outputs (PO1, PO2, PO3)
Rated voltage
250 V AC/DC
Continuous carry
5 A
Make and carry for 3.0 s
15 A
Make and carry for 0.5 s
30 A
Breaking capacity when the control-circuit time constant L/
R <40 ms, at 48/110/220 V DC (PO1 with both contacts
connected in series)
5 A/3 A/1 A
Minimum contact load
100 mA at 24 V AC/DC
Trip-circuit supervision (TCS):
*
Control voltage range
20...265 V AC/DC
*
Current drain through the supervision circuit
~
1.5 mA
*
Minimum voltage over a contact
20 V AC/DC (15...20 V)
Table 5.2.4.-9
Lens sensor and optic fibre for arc protection
Normal service temperature range
-40...+100
°
C
Maximum service temperature range, max 1 h
+140
°
C
Minimum permissible bending radius of the connection
fibre
100 mm
Table 5.2.4.-10
Enclosure class of the flush-mounted relay
Front side
IP 54 Category 2
Rear side, top of the relay
IP 40
Rear side, connection terminals
IP 20
Feeder Protection Relay
Technical Reference Manual - ANSI Version
REF610
REF610
1MRS755535
Содержание RELION REF610
Страница 1: ...Feeder Protection Relay REF610 REF610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 8: ...8 ...
Страница 12: ...12 ...
Страница 14: ...14 ...
Страница 20: ...20 ...
Страница 164: ...164 ...
Страница 175: ......